4 Fault Isolation
4.3 Fault Isolation Concepts
346
HPM High-Performance Process Manager Service
R688
Honeywell
December 2020
Table 62 IOP Box Soft Failure Error Codes
Error
Code
Failure
Mnemonic
Description
Corrective Action
40
EEFAILED
Output EEPROM write failure.
If an HLAI or AO, replace the IOP. If an LLAI,
replace the affected plug-in module.
41
VREFFAIL
LLMUX FTA ref voltage failure
If the problem persists replace the FTA
42
ADOUTUDF
Analog to digital conversion value
underflowed (HLAI only).
Check the input wiring at the FTA; possible bad
contact. Otherwise, replace the IOP card and/or
the FTA.
43
ADOUTCAL
HLAI A/D is out of calibration by more
than ±3%.(refer to the “IOP
Calibration Procedures” section).
Calibrate or replace the IOP card (refer to the
“IOP Calibration Procedures” section).
44
BADFLREG
AO IOP failure selection register is
bad.
Replace the AO IOP card.
45
BDSNDTC
Bad output module secondary latch.
Replace the IOP. Use a Standby Manual device
if nonredundant.
46
BDOUTBFR
Bad output buffer.
Replace IOP. Use Standby Manual device if
nonredundant.
47
VCALFAIL
Calibration reference out of range.
Replace the IOP or recalibrate.
48
F1NOTCAL
LLMux or RHMUX: FTA 1 is not
calibrated.
SI: FTA 1 write buffer has
overflowed.
LLMux or RHMUX: Calibrate FTA 1.
SI: Reduce the number of writes to the FTA.
49
F2NOTCAL
LLMux or RHMUX: FTA 2 is not
calibrated.
SI: FTA 2 write buffer has
overflowed.
LLMux or RHMUX: Calibrate FTA 2.
SI: Reduce the number of writes to the FTA.
50
F1COM_FL
LLMux or RHMUX: FTA 1 fails to
communicate.
SI: FTA 1 fails to communicate.
Check the connection from the Power Adapter
to FTA 1. If the FTA is missing, install the FTA.
If the FTA is present, replace the FTA.
51
F2COM_FL
LLMux or RHMUX: FTA 2 fails to
communicate.
SI: FTA 2 fails to communicate.
Check the connection from the Power Adapter
to FTA 2. If the FTA is missing, install the FTA.
If the FTA is present, replace the FTA.
52
F1_IDERR
FTA #1 is pinned as #1.
Verify/correct the FTA pinning.
53
F2_IDERR
FTA #2 is pinned as #0.
Verify/correct the FTA pinning.
54
F1VREFFL
FTA 1 has a reference voltage
failure.
Replace the FTA.
55
F2VREFFL
FTA 2 has a reference voltage
failure.
Replace the FTA.
56
F1CAL_FL
FTA 1 calibration procedure failed.
Recalibrate the FTA.
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...