2 Equipment Description
2.20 24 Vdc Fuse Protection
106
HPM High-Performance Process Manager Service
R688
Honeywell
December 2020
Right 7-Slot card file
Table 6 Right 7-Slot Card File Backpanel Fuse Protection lists the individual backpanel fuses and their
application for the Right 7-Slot card file. The fuse rating is 2 A for fuse locations F1 through F8.
Right 7-Slot Card File Backpanel Fuse Protection
When HPMM cards occupy the left two slots of a card file, fuse F2 is not in use. Fuse F1 on the
backpanel is used to supply 24 Vdc to the UCN Interface Module.
Table 6 Right 7-Slot Card File Backpanel Fuse Protection
Fuse
Rating
Protection Application
F1
2 A fast-action
Slot 9 IOP card and associated FTA
or
UCN Interface Module (24 Vdc) if HPMM exists in
card file
F2
2 A fast-action
Slot 10 IOP card and associated FTA
F3
2 A fast-action
Slot 11 IOP card and associated FTA
F4
2 A fast-action
Slot 12 IOP card and associated FTA
F5
2 A fast-action
Slot 13 IOP card and associated FTA
F6
2 A fast-action
Slot 14 IOP card and associated FTA
F7
2 A fast-action
Slot 15 IOP card and associated FTA
F8
2 A fast-action
HLAI Optical Coupler Module, U1
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...