2 Equipment Description
2.27 EUCN Cable System
R688
HPM High-Performance Process Manager Service
153
December 2020
Honeywell
Table 19 UCN Node (PM/APM/HPM) Cable Faults (Primary NIM node is a NIM)
Error scenario
UCN COMM STATUS
UCN CABLE
STATUS
$FTESTS2
displays
(this
PM/APM/HPM
with cable faults)
$FTESTS2
displays
(all other
EUCN nodes)
No UCN coaxial
cable problems
A
SIL
B
SIL
A
NSY
B
NSY
OK
UCN: OK/BACKUP
LCN: OK/BACKUP
N/A
N/A
If UCN cable A
on a
PM/APM/HPM
node has a
problem
A
SIL
B
SIL
A
NSY
B
NSY
FAIL
UCN: OK/BACKUP
LCN: OK/BACKUP
N/A
N/A
*
If UCN cable B
on a
PM/APM/HPM
node has a
problem
A
SIL
B
SIL
A
NSY
B
NSY
FAIL
UCN: OK/BACKUP
LCN: OK/BACKUP
N/A
N/A
*
If both UCN cable
A and B on a
PM/APM/HPM
node have a
problem
Primary fails,
Secondary takes
over as primary
A
SIL
B
SIL
A
NSY
B
NSY
FAIL
UCN:
PARTFAIL/OFFNET
LCN: OK/BACKUP
N/A
N/A
*
[1]
*
[1]
Note:
PM/APM/HPM are UCN nodes and hence the $FTESTS displays are not applicable. The FTE
CABLE STATUS field is not available for NIMs.
[1]
Note:
The A SIL, B SIL, A NSY, and B NSY indications only appear for an instant and then shows
blank due to node failure.
Note:
If any SIL or NSY bits are set, then the corresponding cables are backlit on the UCN Status
Display, if the UCN CABLE STATUS target is chosen.
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...