6 Removal and Replacement
6.5 AO Standby Manual Device Operation
R688
HPM High-Performance Process Manager Service
413
December 2020
Honeywell
With the
DIR/REV
switch in the
REV
position, 20 mA equals 0% and 4 mA equals 100%. The
INC
position of the
INC/DEC
switch will decrease current and the
DEC
position will increase current.
Standby Manual device control procedure
Use the HPM Status display to save the Checkpoint for the IOP, and then use the procedure in the
following table to provide Standby Manual device control of the FTA field devices.
Step
Action
1
Be sure all the
OUTPUT SOURCE SELECT
switches are in the
PM
position.
2
Place the
DIR/REV
switches in the correct position for all eight channels.
3
Connect a standard IOP to FTA cable between the
STANDBY MANUAL
connector on
the FTA and the AOSM.
4
Verify that all
OUTPUT SOURCE SELECT
switches are in the
PM
position.
5
The
BALANCE
switch has three positions, left (
CONT
), center (inactive), and right
(
PUSH TO BALANCE
). Select the left or right position.
CONT
Position
In the
CONT
inuous (left) position, the switch remains toggled and all the channels with
their
OUTPUT SOURCE SELECT
switch in the
PM
position will automatically have
their Standby Manual device output level continuously set equal to the IOP level.
Manual
INC
rement and
DEC
rement control for a channel is not possible when a
channel is in the
PM
position while the
BALANCE
switch is in the
CONT
position.
PM
Position
In the
PUSH TO BALANCE
(right) position, the position is momentary and all channels
with their
OUTPUT SOURCE SELECT
switch in the
PM
position will automatically have
their Standby Manual device output level set equal to the IOP output level. However,
this balance method is a single event and the switch returns to the center position when
it is released. Any subsequent change in the IOP’s output level will not be transferred to
the Standby Manual, but the
INC
rement and
DEC
rement control for a channel can alter
the Stand
by Manual device’s current level.
6
The
STANDBY ENABLE
switch can now be depressed. The green LED illuminates to
indicate that the FTA is now ready for control by the Standby Manual device.
7
Placing any or all of the
OUTPUT SOURCE SELECT
switches in the
MAN
ual position
will automatically place all eight IOP channels in the Standby Manual mode.
8
When all eight
OUTPUT SOURCE SELECT
switches are in their
MAN
ual position, the
Analog Output IOP can be placed in the Idle state and removed.
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...