2 Equipment Description
2.13 Field Termination Assembly
R688
HPM High-Performance Process Manager Service
77
December 2020
Honeywell
Galvanically isolated FTAs
Galvanically Isolated type FTAs are listed in the following table.
Table 4 Galvanically Isolated Field Termination Assembly Types
FTA Type
Description
High Level Analog Input
(HLAI/STI)
The HLAI/STI FTA accepts high level analog inputs. Some FTA models also
interface with Smart Transmitter devices. All inputs are isolated from ground and
each other.
24 Vdc Digital Input (DI)
The 24 Vdc DI FTA accepts contact inputs. All inputs are isolated from each
other.
Analog Output (AO)
The AO FTA provides isolated 4-20 mA outputs to proportioning loads such as
valves.
Analog Output (AO) HART
Provides 4-20 mA outputs, and incorporates circuitry to allow HART field devices
to be connected to the FTA without using external filters. These FTAs also
provide a connector for an external HART multiplexer.
24 Vdc Digital Output (DO)
The 24 Vdc DO FTA provides isolated digital outputs to loads such as solenoid
valves or lamps.
Three physical sizes
The standard FTAs have three physical sizes as illustrated in the following figure. The Galvanically
Isolated FTAs are one size only, B-size.
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...