3 UCN Status Displays
3.8 IOP Detail Status Displays
264
HPM High-Performance Process Manager Service
R688
Honeywell
December 2020
I/O Link cable status and statistics
The data in this area is defined in the following table.
The data is updated every four seconds. The area also contains the
RESET MODULE COMM
ERRORS
target, selection of which resets the error/silence totals for the IOP, and resets the
LAST
COMM ERR
field to
NONE
.
Table 53 IOP Detail Status Display
– I/O Link Cable Status/Statistics
Term
Description
ACTIVE CABLE
The current I/O Link receive channel
(CHANNEL A or CHANNEL B)
LAST COMM ERR
The last I/O Link communications error detected by the IOP
CHN A ERR
The total channel A errors detected by the IOP since startup or
the last reset of the cable statistics
CHN B ERR
The total channel B errors detected by the IOP since startup or
the last reset of the cable statistics
CHN A SIL
The total channel A silences detected by the IOP since startup
or the last reset of the cable statistics
CHN B SIL
The total channel B silences detected by the IOP since startup
or the last reset of the cable statistics
Status messages
This area contains status messages that are determined by status bits that are resident in the IOP. The
messages are in pairs as defined in the following table. The first message of each pair is the message that
is displayed if the status bit is on. The status bits can be considered to be independent of one another, so
the message pairs can appear in any combination.
Table 54 IOP Detail Status Display
– I/O Link Cable Status Messages
Term
Description
FTA PRESENT/NO FTA
The presence or absence of a Field Termination
Assembly (FTA) attached to the IOP
WARM START LAST
EXECUTED/COLD
START EXECUTED
The nature of the last IOP startup. A warm startup means
that the IOP’s database has been preserved. A cold
startup means that the IOP has a default database.
STANDBY MANUAL
ENABLED/NO
STANDBY MANUAL
The presence or absence of a Standby Manual device
SWITCHED ACTIVE/NO
SWITCHED ACTIVE
The presence or absence of a switched active device
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...