4 Fault Isolation
4.3 Fault Isolation Concepts
R688
HPM High-Performance Process Manager Service
345
December 2020
Honeywell
Table 62 IOP Box Soft Failure Error Codes
Error
Code
Failure
Mnemonic
Description
Corrective Action
23
OUTPUTFL
Output point failure.
Check which output is failing, then check the
hardware for that output. Replace the hardware
if required.
24
STCKLIM
Internal stack usage in the 8051
processor is close to the limit.
Call TAC for assistance.
25
Not used.
N/A
26
DIAGCTFL
Output loopback circuit is bad.
Replace the appropriate IOP card.
27
ADPCOMFL
I/O Link processor cannot gain
access to the shared RAM. Input
conversion will be prohibited.
Replace the IOP card.
28
NOACLINE
No external ac line is present in the
LLAI. The 6 Vac is used for power
noise cancellation.
Check optical coupler and associated fuse on
the backpanel. Check that the primary (left
side)Power Supply Module in the Power
System is installed and functional.
29
BADPLUGM
Bad plug-in module on the FTA.
Replace the plug-in module.
30
VTESTFAL
Test Volume Reference Failure. PV
is set to NAN by the IOP.
Replace the IOP card.
31
FTAMSMCH
The FTA type and point configuration
are mismatched.
Replace the FTA type or reconfigure.
32
VZERO_FL
Zero Reference Volume failure.The
PV is set to NAN by the IOP.
Replace the IOP card.
33
BADRJVAL
LLAI reference junction value is bad.
Check that the reference junction wire or
jumper (P1) is correctly implemented on the
FTA.
34
BADADPJP
Probable RAM failure in ADP portion.
Replace the LLAI IOP card for the LLAI FTA.
35
ZEROCNFG
Bad configuration byte passed to the
ADP.
Check the configuration.
36
FTA1FAIL
LLMux or RHMUX: FTA 1 has a Soft
failure.
LLMux or RHMUX: Check FTA 1.
SI: Correct the error condition at the device
connected to FTA 1.
37
FTA2FAIL
LLMux or RHMUX: FTA 2 has a Soft
failure.
LLMux or RHMUX: Check FTA 2.
SI: Correct the error condition at the device
connected to FTA 2.
38
CALBABRT
Calibration of an IOP card has been
aborted during the procedure.
Check the precision voltage/resistance source
for accuracy. Also, make sure that the correct
calibration procedure is being followed
39
BADCALRF
Calibration reference input is bad.
Replace the HLAI.
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...