6 Removal and Replacement
6.8 IOP to FTA Cable Replacement
R688
HPM High-Performance Process Manager Service
421
December 2020
Honeywell
6.8 IOP to FTA Cable Replacement
Nonredundant IOP cable replacement
All outputs or inputs carried by the IOP to FTA cable, as well as 24 Vdc from the IOP that powers the
FTA, will be disconnected when the cable is removed. The use of an Analog Output or Digital Output
Standby Manual device may be appropriate to maintain the present outputs of an output type FTA. See
the following subsections of the “Removal and Replacement” section for further discussion.
AO Standby Manual Device Operation
o restore the Checkpoints to the replacement IOP, to select
RUN STATES, and to STARTUP the IOP.
Use the IOP’s slot summary display to adjust the first IOP output to match that
of the Analog O
utput Standby Manual device as follows:
Select the slot, then select the slot’s “OP”, type in a value equal to the current
output fr
om the Standby Manual device for that slot, press the ENTER key.
This allows the IOP to regain FTA output control and provide the same output
level, if so de
sired, that existed before the Analog Output Standby Manual device
position. The IOP will now be controlling channel 1.
Use the point’s Detail or Group display t
o select the Normal mode for the point.
Repeat steps 2 through 5 for IOP channels 2 through 8.
Disconnect the Analog Output Standby Manual device cable
connector on the FTA, if desired.
DO Standby Manual Device Operation.
Redundant IOP cable replacement
Before removing an IOP to FTA cable from a redundant IOP configuration, be sure that the FTA cable to
be removed is not controlling analog output field terminals on the FTA or providing inputs. When the
green
DS1
LED on an AO redundancy FTA is illuminated, the “B” FTA cable can be removed, since the
“A” FTA cable is controlling the FTA output field terminals. When the green DS1 LED on an AO
redundancy FTA is not illuminated, the “A” FTA cable can be removed, since the “B” FTA cable is
controlling the FTA output field terminals. The HPM Status display at the Universal Station can also be
used to determine whether the “A” or “B” FTA cable is controlling the FTA output field terminals.
For critical analog outputs, it is recommended that the “A” AO IOP be removed before the “A” FTA
cable is removed. It is also recommended that the “B” AO IOP be removed before the “B” FTA cable is
removed.
When removing FTA cables from High Level Analog Input (HLAI) IOPs, use the HPM Status display at
the Universal Station to determine whether or not the cable being removed is being used to provide
subsystem inputs.
FTA Replacement
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...