31-00083—02
84
nvoTerminalLoad
SNVT
lev_percent
The effective loading on the controller. A positive value indicates a cooling load and
a negative value will indicate that there is a heating load.
The Terminal Load calculation is controlled by nciCZS.type
Conventional calculation uses the PID output of heating and cooling controls. When
the controller is switched to the heating mode, the Terminal load
≤
0.
-160%
≤
range
≤
160%
CZS calculation uses the Proportional output of heating and cooling controls. When
the controller is switched to the heating mode, the Terminal Load continues to report
both heating and cooling demand. The terminal load absolute value is truncated at
100%
-100%
≤
range
≤
100%
nvoTodEvent
SNVT
tod_event
Network output for scheduled events
currentState
current event state in the controller
0: Occupied
1: Unoccupied
2: Bypass
3: Standby
nextState
scheduled next state in the controller.
0: Occupied
1: Unoccupied
2: Bypass
3: Standby
255: Null
timeToNextState
scheduled time to the next state in the controller
0
≤
range
≤
11520 minutes
nvoUnitStatus
SNVT
hvac_status
VAV Controller status.
Use the application UnitStatus to add this NV to your Lon controller. Refer to the
Appendix for details.
mode
0 – Auto heating and cooling
1 – Heat
2 – Morning warm-up
3 – Cooling
4 – night purge
5- Pre Cool
6 – heating and cooling off
heat_output_primary
Reports the current percentage of ReHeat stages or modulating ReHeat turned on.
When ReHeat is not configured, UnitHeat is set to Invalid.
0 - 100%
heat_output_secondary
Reports the current percentage of peripheral Heat demand. When peripheral Heat
is not configured this value is set to Invalid.
0 – 100%
cool_output
Reports the current percentage of cooling air delivered to the zone.
0 – 100%
econ_output
Set to invald
Table 22. Network Variable - Outputs (Continued)
Nv/field
Net Data Type
Description