79
31-00083—02
HeatStages
3bits
Heating stages active
0
≤
range
≤
3
PeriphHeatOn
Ubit
Peripheral heat stage 1
0: inactive
1: active
AuxOn
Ubit
Auxiliary circuit status
0 - effective occupancy is not Occ
1- effective occupancy is Occ
FanOn
Ubit
Fan digital output status
0 – off
1 – on
DlcShed
Ubit
Indicates the status of the Demand limit control load shed.
0 – inactive
1 – active
HeatCoolSwitch
Ubit
Heat Cool Change Over Switch
0 – Cool Mode (cool air is supplied to the ZT)
1 – Heat Mode (warm air is supplied to the ZT)
WindowOpen
Ubit
indicates the current state of the window sensors (local input, network input or Share
input)
1 - that the window is open
0 - that the window is closed.
LowFlowAlarm
Ubit
Low airflow alarm
0 – inactive
1 – active
IaqOvr
Ubit
IAQ override alarm. The space CO2 sensor exceeds the high limit.
0 – inactive
1 – active
Free1On
Ubit
Free digital output # 1 status. Controlled by network input nviFree1
0 – inactive
1 – active
MonSwitch
Ubit
The state of the digital input wired to a general purpose monitor switch
1 - switch is closed
0 - switch is open
SpcTempAlm
Ubit
Occupied Space Temperature alarm
0 – inactive
1 – active
Future
2bits
nvoCtlDataG2
Node Status Group – Analog Data
This is a limited summary of VAV analog data intended for Workstation Graphics.
TempControlPt
SNVT
temp_p
Space temperature effective setpoint
40
≤
range
≤
100F
SpaceTemp
SNVT
temp_p
Space temperature
14
≤
range
≤
122F
SpaceCO2
SNVT
ppm
Space CO2
0
≤
range
≤
5000 PPM
Invalid = 65535
SpaceRH
SNVT
lev_cont
Space relative humidity
0
≤
range
≤
100%
Invalid = 127.5
DischargeTemp
SNVT
temp_p
Discharge air temperature setpoint
-49
≤
range
≤
233.6 F
SupplyTemp
SNVT
temp_p
Duct in supply air temperature.
32
≤
range
≤
212 F
FreshAirRatio
SNVT
lev_percent
100 * (FreshAirRequired / BoxFlow)
0
≤
range
≤
150%
Table 22. Network Variable - Outputs (Continued)
Nv/field
Net Data Type
Description