31-00083—02
16
IMPORTANT:
Power must be off prior to connecting to or removing
connections from the 24 Vac power (24 Vac/24 Vac COM),
earth ground (EGND), and 20 Vdc power (20 Vdc) terminals.
IMPORTANT:
Use the heaviest gauge wire available, up to 14 AWG (2.0 sq
mm), with a minimum of 18 AWG (1.0 sq mm), for all power
and earth ground wiring. Screw-type terminal blocks are
designed to accept up to one 14 AWG (2.0 sq mm) conductor
or up to two 18 AWG (1.0 sq mm) conductors. More than two
wires that are 18 AWG (2.0 sq mm) can be connected with a
wire nut. Include a pigtail with this wire group and attach the
pigtail to the terminal block.
IMPORTANT:
If the controller is used on
Heating and Cooling Equipment
(UL 1995, U.S. only)
and the transformer primary power is
more than 150 volts, connect terminal 2, (the 24 Vac common
[24 VAC COM] terminal) to earth ground (see Fig. 14). For
these applications, only one controller can be powered by
each transformer.
Fig. 13. Power wiring details for one controller per
transformer
Fig. 14. Transformer power wiring details for one
controller used in UL 1995 equipment (U.S. only).
More than one controller can be powered by a single
transformer. Fig. 15 shows power wiring details for multiple
controllers.
NOTE:
Controller configurations are not necessarily limited to
three devices, but the total power draw, including accessories,
cannot exceed 100 VA when powered by the same
transformer (U.S. only). For power wiring recommendations,
see "Power" on page 13.
Fig. 15. Power wiring details for two or more controllers per transformer
CONNECT POWER TO
TERMINALS 1 AND 2
EARTH
GROUND
(TERMINAL 3)
TRANSFORMER
OUTPUT
DEVICE
POWER
M33634
COM
24 VAC
Δ
P
1 1 1 1 1 1 1 2 2 2 2 2
3 4 5 6 7 8 9 0 1 2 3 4
UI-4
COM
UI-3
UI-2
COM
UI-1*
AO
-2
COM
AO
-1
COM
DO-2
DO-1
1 1
1 2 3 4 5 6 7 8 9 0 1 2
COM
DO-4
COM
DO-3
NET
-2
NE1-2
S-B
U
S 2
S-B
U
S 1
20VDC
EGND
24V
A
C
COM
24V
A
C
Δ
P
1 1 1 1 1 1 1 2 2 2 2 2
3 4 5 6 7 8 9 0 1 2 3 4
UI-4
COM
UI-3
UI-2
COM
UI-1*
AO
-2
COM
AO
-1
COM
DO-2
DO-1
1 1
1 2 3 4 5 6 7 8 9 0 1 2
COM
DO-4
COM
DO-3
NET
-2
NE1-2
S-B
U
S 2
S-B
U
S 1
20VDC
EGND
24V
A
C
COM
24V
A
C
M33635
EARTH
GROUND
(TERMINAL 3)
TRANSFORMER
OUTPUT
DEVICE
POWER
EARTH
GROUND
1
LINE VOLTAGE
GREATER
THAN 150 VAC
IF THE CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE
PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND 24 VAC COM
SIDE OF TRANSFORMER SECONDARY.
1
COM
24 VAC
CONNECT POWER TO
TERMINALS 1 AND 2
Δ
P
1 1 1 1 1 1 1 2 2 2 2 2
3 4 5 6 7 8 9 0 1 2 3 4
UI-4
COM
UI-3
UI-2
COM
UI-1*
AO
-2
COM
AO
-1
COM
DO-2
DO-1
1 1
1 2 3 4 5 6 7 8 9 0 1 2
COM
DO-4
COM
DO-3
NET
-2
NE1-2
S-B
U
S 2
S-B
U
S 1
20VDC
EGND
24V
A
C
COM
24V
A
C
M33636
120/240
VAC
TRANSFORMER
OUTPUT
DEVICE
POWER
COM
24 VAC
EARTH
GROUND (TERMINAL 3)
EARTH
GROUND (TERMINAL 3)
EARTH
GROUND (TERMINAL 3)
CONNECT POWER TO
TERMINALS 1 AND 2
1 1 1 1 1 1 1 2 2 2 2 2
3 4 5 6 7 8 9 0 1 2 3 4
UI-4
COM
UI-3
UI-2
COM
UI-1*
AO
-2
COM
AO
-1
COM
DO-2
DO-1
1 1
1 2 3 4 5 6 7 8 9 0 1 2
COM
DO-4
COM
DO-3
NET
-2
NE1-2
S-B
U
S 2
S-B
U
S 1
20VDC
EGND
24V
A
C
COM
24V
A
C
1 1 1 1 1 1 1 2 2 2 2 2
3 4 5 6 7 8 9 0 1 2 3 4
UI-4
COM
UI-3
UI-2
COM
UI-1*
AO
-2
COM
AO
-1
COM
DO-2
DO-1
1 1
1 2 3 4 5 6 7 8 9 0 1 2
COM
DO-4
COM
DO-3
NET
-2
NE1-2
S-B
U
S 2
S-B
U
S 1
20VDC
EGND
24V
A
C
COM
24V
A
C