57
31-00083—02
nciFloat1
Configure floating output
Pin1 = DO3 (DO must be configured binary, nciDO3.type =
0)
Pin2 = DO4 (DO must be configured binary, nciDO4.type =
0)
Note:
To free up binary outputs DO3 & DO4, set the travelTime = 0
action
ubyte
0
Reverse action
0: False 100%=full open, 0% = full closed
1: True 100%=full closed, 0% = full open
travelTime
SNVT_
time_sec
90
Motor travel time
0
≤
range
≤
3276.7 sec
Precision: 1
Notes:
Set the travel time to zero to disable the Floating Output and
free up DO3 & DO4
autoSync
ubyte
0
Auto Sync Type
0: none
1: Sync closed
2: Sync open
Refer to Appendix E – Floating Actuator Auto Synch
syncIntvl
SNVT_
time_hour
24
Auto sync interval
0
≤
range
≤
254 hours
Precision: 1
pwrUpSync
ubyte
0
Power up Sync Type
0: none
1: Sync closed
2: Sync open
Refer to Appendix E – Floating Actuator Auto Synch
pwrUpDelay
SNVT_
time_sec
0
Actuator Power up delay.
0
≤
range
≤
3276.7 sec
Precision: 1
UnOccSync
ubyte
0
Sync the floating actuator on an occupancy transition to
unoccupied.
0: none
1: Sync closed
2: Sync open
NviSync
ubyte
0
Sync the floating actuator on an active nviFree1Dig signal.
0: none
1: Sync closed
2: Sync open
Table 18. Local Output Configuration (Continued)
NCI/Field
Net Data Type Default Val
Description