83
31-00083—02
Mode
SNVT
count_inc
Master Node Status
0 - Startup wait
1 - Heat
2 - Cool
3 - Reheat
4 – Morn_Warm
5 – Night Purge
6 – Pressurize
7 – Depressurize
8 – Trackflow
9 – Manual Damper Position
10 – Manual Flow
11 - Freeze Protect
12 – Factory Test.
Not supported Note 1
13 – IO Test
Not Supported. Note 1
14 – Float out sync
Not Supported.
15 – Disabled
Not Supported. Note 1
16 – Manual
Not Supported. Note 1
17 – Emerg Command Purge
18 – Emerg Command Shutdown
19 – Htg & Clg disabled.
20 – Fan only
Notes:
1. Refer to nvoNodeStatus.manual_control
ReheatStg
SNVT
count_inc
indicates the number of stages that should be turned on in the receiving nodes
0
≤
range
≤
3
ReheatCmd
SNVT
lev_percent
indicates the amount of modulating ReHeat that should be turned on in the receiving
nodes.
0
≤
range
≤
100%
TempFlowCmd
SNVT
lev_percent
Output command of the temperature control loop in terms of percentage (%) of flow
capacity mapped to the minimum - maximum flow range (zero percent as minimum
flow and 100% as maximum flow).
0
≤
range
≤
100%
EffectOcc
SNVT
occupancy
Effective occupancy
PeriphStg
SNVT
count_inc
indicates the number of peripheral heat stages that should be turned on in the
receiving nodes
0
≤
range
≤
1
PeriphCmd
SNVT
lev_percent
indicates the amount of modulating peripheral heat that should be turned on in the
receiving nodes.
0
≤
range
≤
100%
nvoSpaceCO2
SNVT
ppm
Space CO2 concentration.
0
≤
range
≤
5000 PPM
nvoSpaceHum
SNVT
lev_percent
Space relative humidity.
0
≤
range
≤
100%
nvoSpaceTemp
SNVT
temp_p
The space temp value available to the network
14
≤
range
≤
122F
nvoStaticP
SNVT
press_f
Building or Duct static pressure. This is a data value obtained from a spare local
input. It is typically network connected to a central VAV fan control.
-1.3433e36
≤
range
≤
1.3433e36 inWc
nvoSupplyTemp
SNVT
temp_p
Duct in cooling supply temperature.
32
≤
range
≤
212 F
Table 22. Network Variable - Outputs (Continued)
Nv/field
Net Data Type
Description