31-00083—02
82
nvoReheatPos
SNVT_
lev_percent
Reheat commanded control position.
-163%
≤
range
≤
163%
nvoReheatStgs
count
Number of active heating coil stages.
0
≤
range
≤
3
nvoSbusSensors
ZioTemp
SNVT
temp_p
Calibrated Zio wall module temperature value.
Output = Sbu nciWallModZio.TempOffset
30
≤
range
≤
110F
ZioRh
SNVT_
lev_percent
Calibrated Zio wall module RH value
Output = Sbu nciWallModZio.RhOffset
0
≤
range
≤
100%
C7400Temp
SNVT
temp_p
Calibrated C7400s temperature value
Output = Sbu nciSbusSnsr.TempOffset
-40
≤
range
≤
150F
C7400Rh
SNVT_
lev_percent
Calibrated C7400s RH value
Output = Sbu nciSbusSnsr.RhOffset
0
≤
range
≤
100%
nvoSensorOcc
SNVT
occupancy
OccSensorOut is an output showing the current state of the hard wired occupancy
sensor. The valid enumerated states are listed below:
nvoShare
In some cases a sending node(master VAV controller) with a wall module may be
used to control the Damper, ReHeat and Peripheral heat of one or more other
receiving nodes (satellite VAV controllers) that do not have a wall module. To use
this feature:
All nodes involved must be configured to have the same kind of ReHeat via
ReHeatType.
The satellite receiving nodes must have FlowControlType set to ShareWallModule.
The satellite receiving nodes must have nviShare bound to nvoShare of a node
having a wall module.
Table 22. Network Variable - Outputs (Continued)
Nv/field
Net Data Type
Description
State
Meaning
0 Occ
The space is occupied
1 UnOCC The space is not occupied
255 Null
The occupancy sensor is not configured