55
31-00083—02
PeriphHtgMin
ubyte
255
Peripheral heating valve minimum position. Typically used to connect an
accessory loop reset schedule.
0
≤
range
≤
255
Table 17. Logical Input Configuration (Continued)
NCI/Field
Net Data
Type
Default
Val
Description
36 nviFree1Mod_levPercentoutSnapshot
47 AccPid1OUTPUTSnapshot
48 AccPid2OUTPUTSnapshot
49 Acc1ResetEFF_OUTPUTSnapshot
50 Acc2ResetEFF_OUTPUTSnapshot
255 Undefined
Table 18. Local Output Configuration
NCI/Field
Net Data Type Default Val
Description
nciAO1
Configure local analog output
analogRng
ubyte
0
Analog range selection
0: 0 to 10 vdc (AO_0_10vdcDir)
1: 10 to 0 vdc (AO_0_10vdcRev)
2: 2 to 10 vdc (AO_2_10vdcDir)
3: 10 to 2 vdc (AO_2_10vdcRev)
4: 0 to 20 mA (AO_0_20maDir)
5: 20 to 0 mA (AO_0_20maRev)
6: 0 to 22 mA (AO_0_22maDir)
7: 22 to 0 mA (AO_0_22maRev)
8: 4 to 20 mA (AO_4_20maDir)
9: 20 to 4 mA (AO_4_20maRev)
10: Binary output (AO_Binary)
nciAO2
Configure local analog output
analogRng
ubyte
0
Analog range selection
0: 0 to 10 vdc (AO_0_10vdcDir)
1: 10 to 0 vdc (AO_0_10vdcRev)
2: 2 to 10 vdc (AO_2_10vdcDir)
3: 10 to 2 vdc (AO_2_10vdcRev)
4: 0 to 20 mA (AO_0_20maDir)
5: 20 to 0 mA (AO_0_20maRev)
6: 0 to 22 mA (AO_0_22maDir)
7: 22 to 0 mA (AO_0_22maRev)
8: 4 to 20 mA (AO_4_20maDir)
9: 20 to 4 mA (AO_4_20maRev)
10: Binary output (AO_Binary)
nciDO1
Configure local digital output
type
ubyte
0
Digital output type
0: Binary output
1: Pulse width modulating output