7
31-00083—02
SPECIFICATIONS
Electrical
Rated Voltage:
20-30 Vac; 50/60 Hz
Power Consumption:
100 VA for controller and all connected loads
Controller only Load:
5 VA maximum, model CVL4024NS-
VAV1
Controller and Actuator Load:
9 VA maximum, model
CVL4022AS-VAV1
External Sensors Power Output:
20 Vdc ±10% @ 75 mA
maximum
Environmental
Operating & Storage Temperature Ambient Rating
Minimum 32° F (0° C); Maximum 122° F (50° C)
Relative Humidity:
5% to 95% non-condensing
Approval Bodies
UL/cUL (E87741) listed under UL916 (Standard for Open
Energy Management Equipment) with plenum rating.
CSA (LR95329-3) listed.
Meets FCC Part 15, Subpart B, Class B (radiated emissions)
requirements.
Meets Canadian standard C108.8 (radiated emissions).
Conforms to the following requirements per European
Consortium standards:
- EN 61000-6-1; 2001 (EU Immunity).
- EN 61000-6-3; 2001 (EU Emissions)
Velocity Pressure Sensor
Operating Range:
0 to 1.5 in. H2O (0 to 374 Pa)
Series 60 Floating Actuator
Rotation Stroke:
95° ± 3° for CW or CCW opening dampers
Torque Rating:
44 lb-in. (5 Nm)
Run Time for 90° rotation: 90 seconds at 60 Hz
Hardware
CPU:
Each controller uses a Texas Instruments MSP430 fam-
ily microprocessor. The processor contains on-chip FLASH
program memory, FLASH information memory, and RAM.
Memory Capacity
Flash Memory:
116 kilobytes with 8 kilobytes available for
user program. The controller is able to retain FLASH mem-
ory settings for up to ten (10) years.
RAM:
8 kilobytes
Dimensions
H/W/D: 5.45 x 6.85 x 2.26 in. (13.84 x 17.40 x 5.74 cm)
Real Time Clock
Operating Range:
24 hour, 365 day, multi-year calendar
including day of week and configuration for automatic day-
light savings time adjustment to occur at 2:00 a.m. local
time on configured start and stop dates.
Power Failure Backup:
24 hours at 32 to 100° F (0 to 38° C),
22 hours at 100 to 122° F (38 to 50° C)
Accuracy:
±1 minute per month at 77° F (25° C)
Inputs and Outputs
CVL4022AS-VAV1 has four universal input (UI) circuits, two
analog outputs (AO), and two digital Triac outputs (DO).
Two Digital Outputs are reserved for the actuator.
CVL4024NS-VAV1 has four universal input (UI) circuits, two
analog outputs (AO), and four digital Triac outputs (DO).
Universal Input (UI) Circuits
See Table 4 for the UI specifications.
Table 4. Universal Input Circuit Specifications
Input
Type
Sensor
Type
Operating
Range
Room/Zone
Discharge Air
Outdoor Air
Supply Air
Temperature
20K Ohm
NTC
-40° F to 199° F
(-40° C to 93° C)
Outdoor Air
Temperature
C7031G
a
a
C7031G and C7041F are recommended for use with these
controllers, due to improved resolution and accuracy when
compared to the PT1000.
Analog Output (AO) Circuits
ANALOG CURRENT OUTPUTS:
Current Output Range: 4.0 to 22.0 mA
Output Load Resistance: 550 Ohms maximum
ANALOG VOLTAGE OUTPUTS:
Voltage Output Range: 0 to 11 V
Output minimum load restistance: 600 Ohms
Switchover point from current to voltage is approximately
570 Ohms
Digital Triac Output (DO) Circuits
Voltage Rating: 20 to 30 Vac @ 50-60Hz
Current Rating: 25 mA to 500 mA continuous, 800 mA (AC
rms) for 60 milliseconds
-40° to 120°F
(-40° to 49°C)
C7041F
a
-40° to 250°F
(-40° to 121°C)
PT1000
(IEC751 3850)
-40° F to 199° F
(-40° C to 93° C)
TR23
Setpoint
Potentiometer
500 Ohm
to
10,500 Ohm
-4° DDC to 4° DDC
(-8° DDF to 7° DDF)
or
50° F to 90° F
(10° C to 32° C)
Resistive Input
Generic
100 Ohms
to
100K Ohms
Voltage
Input
Transducer,
Controller
0–10 Vdc
Discrete Input
Dry Contact
closure
OpenCircuit 3000Ohms
≥
ClosedCircuit 3000
<