95
31-00083—02
nciPwrUpDisable
SNVT
time_sec
10
sec
Controller power up disable time. Local logical digital outputs are
disabled for a fixed time at power up. Emergency mode bypasses
the power up disable.
1
≤
range
≤
300 sec
Precision: 0
nciRecovClg
MaxClRmp
∆
F/hr
6
∆
F/hr
Max cooling setpoint ramp
0
≤
range
≤
36
∆
F/hr
Precision: 3
MinClRmp
∆
F/hr
2
∆
F/hr
Min cooling setpoint ramp
Cooling recovery rate when an outdoor air temperature sensor
value is not available.
0
≤
range
≤
36
∆
F/hr
Precision: 3
OTMxClRmp
SNVT
temp_p
70
F
Outdoor air temperature at the max cooling ramp
-30
≤
range
≤
120 F
Precision: 1
OTMnClRmp
SNVT
temp_p
90
F
Outdoor air temperature at the min cooling ramp
-30
≤
range
≤
120 F
Precision: 1
nciRecovHtg
MaxHtRmp
∆
F/hr
8
∆
F/hr
Max heating setpoint ramp
0
≤
range
≤
36
∆
F/hr
Precision: 3
MinHtRmp
∆
F/hr
2
∆
F/hr
Min heating setpoint ramp.
Heating recovery rate when an outdoor air temperature sensor
value is not available.
0
≤
range
≤
36
∆
F/hr
Precision: 3
OTMxHtRmp
SNVT
temp_p
60
F
Outdoor air temperature at the max heating ramp
-30
≤
range
≤
120 F
Precision: 1
OTMnHtRmp
SNVT
temp_p
0
F
Outdoor air temperature at the min heating ramp
-30
≤
range
≤
120 F
Precision: 1
nciSpSpcFrz
SNVT
temp_p
46.4
F
Space freeze protection setpoint.
The space heating setpoint is shifted to this value when a window
is opened.
-30
≤
range
≤
70 F
Precision: 1
nciSpcTempAlm
HiLimit
SNVT
temp_p
90
F
Space temperature occupied alarm high limit
LoLimit < range
≤
100F
Precision: 1
LoLimit
SNVT_
temp_p
50
F
Space Temperature occupied alarm low limit
40F
≤
range < HiLimit
Precision: 1
Delay
SNVT_
time_min
1800
sec
Space Temp alarm disable delay from a change to occupied.
0
≤
range
≤
32767 sec
Precision: 0
Table 23. Configuration Parameters (Continued)
NCI/Field
Net Data
Type
Default
Val
AP
Internal
Units
Description