87
31-00083—02
FractionOfMaxAirFlow
float
0.0
Fraction of maximum airflow added to the minimum airflow
setpoint while coordinating CO2 with the effective airflow setpoint.
0
≤
range
≤
1.0
Precision: 3
Notes:
Set this value to zero to disable CO2 ventilation.
nciCool
TR Temp-Delta
∆
F
3
∆
F
Cooling throttling range
2
≤
range
≤
30
∆
F
Precision: 0
IT
Time
sec
4000
sec
Cooling integral time
0
≤
range
≤
9000 sec
Precision: 0
DT
Time
sec
0
sec
Cooling derivative time
0
≤
range
≤
9000 sec
Precision: 0
ncidlcShiftSpt
SNVT
temp_diff_p
3
F
Demand limit shed setpoint shift. The room space temperature
cooling setpoint is shifted up and the heating setpoint is shifted
down by this value during a DLC active event.
0
≤
range
≤
10
∆
F
Precision: 1
nciCZS
Commercial Zoning System Configuration
type
ubyte
0
NA
CZS type
0: use conventional zone terminal load calculation.
1: use CZS zone terminal load calculation.
Notes:
Refer to nvoTerminalLoad for details on terminal load calculation.
subType
ubyte
0
NA
Future SubType configuration for CZS.
nciDuctArea
SNVT
area
0.5454
sqFt
The area of the cooling duct where the flow sensor is installed.
0 < range
≤
100 sqFt
Precision: 3
nciFan
Table 23. Configuration Parameters (Continued)
NCI/Field
Net Data
Type
Default
Val
AP
Internal
Units
Description
Duct Dia
(in)
Area
(sq ft)
2
0.0218
4
0.0873
6
0.1963
8
0.3491
10
0.545
12
0.7854
14
1.069
18
0.7671
20
2.1817
22
2.6398
24
3.1416