97
31-00083—02
Type
ubyte
2
Wall module type
0: None
1: Conventional Wall module(TR20)
2: Zio TR71 or TR75
MinHtgSetPt
SNVT
temp_p
0
F
Low limit on occupied heating setpoint.
0F
≤
range
≤
MaxHtgSetPt
Precision: 1
MaxHtgSetPt
SNVT
temp_p
100
F
High limit on occupied heating setpoint.
MinHtgSetPt
≤
range
≤
100F
Precision: 1
MinClgSetPt
SNVT
temp_p
0
F
Low limit on occupied cooling setpoint.
0F
≤
range
≤
MaxClgSetPt
Precision: 1
MaxClgSetPt
SNVT
temp_p
100
F
High limit on occupied cooling setpoint.
MinClgSetPt
≤
range
≤
100F
Precision: 1
nciWallModConv
Conventional Wall Module Configuration. Used by the Tool set the
bypass override operation.
OvrdType
ubyte
0
Override Type
0: Normal
1: Bypass Only
2: Disabled
Note:
The nciWallModCom.Type = 1 (TR20) to enable the TR20 override
push button.
nciWallModZio
Zio Wall Module Config
These configuration parameters are used by the Tool set Zio
functionality.
Notes:
Occupant override is not a configurable option. The TASOWiz Zio
has a fixed override feature set:
Occupied
with fixed interval configured by:
nciWallModCom.BypassTime
0
≤
range
≤
65535 min
UnOccupied
with a Zio user selectable UnOccupied override
interval:
1
≤
range
≤
99 days
Sbus Address = 1 (rotary switch = 1)
TempUnits
ubyte
0
Home Screen Temperature Sensor display engineering units
0= DegF
1= DegC
ClkFormat
ubyte
0
12/24 hour clock format
0= 12Hr,
1= 24Hr
SysMode
ubyte
0
System Mode Type. (Future)
0: No system mode on home screen,
1: Heat only (Off/Heat)
2: Cool only (Off/Cool)
3: Heat and Cool (Off/Cool/Heat),
4: Autochangeover
(Off/Auto/Cool/Heat),
5: HeatPump
(Off/Auto/Cool/EmrgHeat/Heat)
Notes:
This is a future field not supported in the current release.
Table 23. Configuration Parameters (Continued)
NCI/Field
Net Data
Type
Default
Val
AP
Internal
Units
Description