77
31-00083—02
FanOvrd
UBIT
Fan in manual override state.
Frost
UBIT
Space low temperature (42.8F) alarm
IAQalm
UBIT
The indoor air quality sensor has detected that the indoor air quality is poorer than
the desired standard. Alarm disabled when not occupied or freeze protect mode.
InvalidSP
UBIT
One of the Set Points is not in the valid range.
The node issues an INVALID_SET_POINT alarm when:
(1) Any set point lies outside the 40F to 100F range
(2) unoccupied heat > occupied heat
(3) occupied heat > occupied cool
(4) occupied cool > unoccupied cool
(5) standby heat > standby cool
SpaceTemp
UBIT
Occupied space temperature alarm. Alarm locked out until the space effective
occupancy is occupied and after a fixed delay. Refer to nciSpcTempAlm for
configuration details.
Alm1
UBIT
Future alarm.
Alm2
UBIT
Future alarm.
Alm3
UBIT
Future alarm.
Alm4
UBIT
Future alarm.
Alm5
UBIT
Future alarm.
Alm6
UBIT
Future alarm.
Alm7
UBIT
Future alarm.
nvoBoxFlow
SNVT_
flow
The airflow output of the VAV Box cooling stream.
0
≤
range
≤
138850 cfm
nvoBypass
SNVT
switch
This allows a wall module at one node to be used to over ride the scheduled
occupancy of another node. The node with nviBypass bound normally does not
have a wall module. See the EffectOcc and OverRide for more details.
Note: Do not enable Guaranteed Periodic Update (GPU) for this NV.
state
value
nvoCtlDataG1
Node Status Group - Binary & Enumerated Data
This is a limited summary of VAV binary and enumerated data intended for
Workstation Graphics. This NV is suitable for data transfer using a network NV
binding or polling. Since the Significant event notification is set to a zero value, the
polled information is always current.
Table 22. Network Variable - Outputs (Continued)
Nv/field
Net Data Type
Description
State
Value
Description
0
0
Override is not Bypass
1
100
Override is Bypass