31-00083—02
80
BoxFlowControlPt
SNVT
flow
Box airflow setpoint
0
≤
range
≤
138850 cfm
BoxFlow
SNVT
flow
Box airflow
0
≤
range
≤
138850 cfm
DamperPos
SNVT
lev_cont
Airflow damper position
0
≤
range
≤
100
ReheatPos
SNVT
lev_cont
Reheat valve position
0
≤
range
≤
100
PeriphHeatPos
SNVT
lev_cont
Peripheral heating valve position
0
≤
range
≤
100
FanSpd
SNVT
lev_cont
Fan speed in percent
0
≤
range
≤
100
Invalid = 127.5
Free1Mod
SNVT
lev_cont
Free modulating output controlled by nviFree1
0
≤
range
≤
100
Invalid = 127.5
nvoDamperPos
SNVT
lev_percent
The position of the cooling air damper.
0%: closed
100%: Open
0
≤
range
≤
100%
nvoDlcShed
SNVT
switch
Indicates the state of nviDlcShed.
nvoDschrgAirTemp
SNVT
temp_p
Discharge air temperature
-49
≤
range
≤
233.6 F
nvoEffCnrSetPt
SNVT
temp_p
Effective space temperature center setpoint.
EffCntrSetPt = Ef ((EffClgSP – EffHtgSP)/2)
-30
≤
range
≤
100F
nvoEffControlDb
SNVT_
temp_diff_p
Effective temperature control deadband.
EffControlDb = EffClgSP – EffHtgSP
0
≤
range
≤
60
∆
F
nvoEffectFlowCSP
SNVT
flow
The effective airflow setpoint.
0
≤
range
≤
138850 cfm
nvoEffectMode
SNVT
hvac_mode
Effective network commanded HVAC Mode
0 – Auto heating and cooling
1 – Heat
2 – Morning warm-up
3 – Cooling
4 – night purge
6 – heating and cooling off
9 – Fan Only, no heating or cooling
nvoEffectOccup
SNVT
occupancy
The effective occupancy state.
0: Occupied
1: Unoccupied
2: Bypass
3: Standby
nvoEffectSetPt
SNVT
temp_p
The effective space temperature setpoint.
-30
≤
range
≤
100F
Table 22. Network Variable - Outputs (Continued)
Nv/field
Net Data Type
Description
State
Value
Meaning
0
0
DLC input inactive
1
100
DLC input active
Null
Null
DLC input inactive