31-00083—02
54
WallModOvrdBut
ubyte
255
Wall module occupancy override button. Typically used with the
conventional wall module. Must be connected to UI1 on Spyder Micro
hardware.
Application Units: Binary Value
0
≤
range
≤
255
Notes:
If 4 (DI_1) is selected, UI_1 is inactive and cannot be assigned to another
logical input.
Override Type = Normal
Override Type = Bypass Only
Table 17. Logical Input Configuration (Continued)
NCI/Field
Net Data
Type
Default
Val
Description
4
DI_1outLive
255 Undefined
Override
Button Held
Down
LED
WM
Override
Comment
0.2 to 1.1
second
OFF
OCCNUL No Override (cancel)
1.2 to 4
seconds
ON
BYPASS Timed Occupied Override
Timer (re)loaded whenever the
button is pressed for this
duration.
WM Override is set to OCCNUL
when timer expires.
4.1 to 7
seconds
1 flash/
sec
UNOCC
Unoccupied Override
Longer than
7.1 seconds
OFF
OCCNUL No Override (cancel)
Override
Button Held
Down
LED
WM
Override
Comment
0.2 to 1.1
second
OFF
OCCNUL No Override (cancel)
1.2 to 4
seconds
ON
BYPASS Timed Occupied Override
Timer (re)loaded whenever the
button is pressed for this
duration.
WM Override is set to OCCNUL
when timer expires.
4.1 to 7
seconds
OFF
OCCNUL No Override (cancel)
Longer than
7.1 seconds
OFF
OCCNUL No Override (cancel)