31-00083—02
96
nciTempSetpoints
SNVT
temp_setpt
Room Temperature setpoints.
40
≤
range
≤
100F
Precision: 1
unoccupied_heat
≤
standby_heat
≤
occupied_heat
≤
occupied_cool
≤
standby_cool
≤
unoccupied_cool
occupiedCool
74
F
standbyCool
76
F
unoccupiedCool
85
F
occupiedHeat
70
F
standbyHeat
67
F
unoccupiedHeat
60
F
nciWallModCom
Wall Module configuration common to Zio and Conventional
BypassTime
SNVT
time_min
180
min
BypassTime is the time between the pressing of the over ride
button at the wall module (or initiating Bypass via ManOccIn) and
the return to the original occupancy state.
0
≤
range
≤
1092 min
Precision: 0
Notes:
To disable bypass in Zio, set this value to zero.
UseWmStPt
ubyte
0
UseWallModStPt specifies the center set point temperature source
when the effective occupancy is Occ. If UseWMStPt is 1, then,
based on the type of set point knob configured, then “temporary”
variables OccHeat and OccCool are changed as shown below:
Type of SetPoint
Direct
OccHeat = WallModSetPt - ZEB / 2
OccCool = WallMo ZEB / 2
Offset
OccHeat = O WallModSetPt
OccCool = O WallModSetPt
0 – Ignore Wall Module Setpt
1 – Use Wall Module SetPt
Notes:
The Wall Module center setpoint is active only when the effective
occupancy is Occupied or Bypass.
LowSetPt
float
-10
Low limit on wall module occupied center setpoint
-10
≤
range
≤
100
Precision: 1
Notes:
The center setpoint high & low limit are unit less since the center
point value can be in F or
∆
F.
If you are using a Conventional Wall Module relative setpoint, the
low limit must be greater than -10F. That is, a value of -10F is
interpreted as -10F absolute.
HighSetPt
float
100
High limit on the wall module occupied center setpoint.
-10
≤
range
≤
100
Precision: 1
Notes:
The center setpoint high & low limit are unit less since the center
point value can be in F or
∆
F.
If you are using a Conventional Wall Module relative setpoint, the
high limit must be less than +10F. That is, a value of +10F is
interpreted as +10F absolute.
Table 23. Configuration Parameters (Continued)
NCI/Field
Net Data
Type
Default
Val
AP
Internal
Units
Description