91
31-00083—02
FilterFlow
ubyte
0
Airflow low pass (10 sec time constant) filter enable. Warning:
Enable filter only when the pressure pickup is installed in a
turbulent airflow environment with unstable airflow control issues.
0: filter disabled
1: filter enabled
Notes:
Set nciFlowLoop.DeadBand = 30 fpm when filter enabled
nciFlowSP
StbyMinFlowPos
SNVT
lev_percent
0
%
VAV Box standby mode of operation minimum flow setpoint in
damper position percent. Applies only to pressure dependent
control mode.
0
≤
range
≤
MaxFlowPos
Precision: 1
UnOcMinFlowPos
SNVT
lev_percent
0
%
VAV Box unoccupied mode of operation minimum flow setpoint in
damper position percent. Applies only to pressure dependent
control mode.
0
≤
range
≤
MaxFlowPos
Precision: 1
MinFlowPos
SNVT
lev_percent
15
%
Zone terminal minimum cooling flow setpoint during the occupied
mode of operation. Applies only to pressure dependent control
mode or when a pressure independent airflow sensor fails.
0
≤
range
≤
MaxFlowPos
Precision:1
MaxFlowPos
SNVT
lev_percent
60
%
VAV Box Maximum Cooling flow value in damper position percent.
Applies only to pressure dependent control mode or when a
pressure independent airflow sensor fails.
0
≤
range
≤
100%
Precision:1
ReheatFlowPos
SNVT
lev_percent
20
%
VAV Box Reheat cooling air value in damper position percent. The
cooling air damper will be at the ReheatPos at maximum reheat
capacity.
0
≤
range
≤
MaxFlowPos
Precision: 1
EmergPress
SNVT
lev_percent
100
%
Emergency pressurization setting as a percent of maximum flow.
0
≤
range
≤
100%
Precision: 1
EmergDePress
SNVT
lev_percent
0
%
Emergency depressurization setting as a percent of maximum
flow.
0
≤
range
≤
100%
Precision: 1
EmergPurge
SNVT
lev_percent
50
%
Emergency purge setting as a percent of maximum flow.
0
≤
range
≤
100%
Precision: 1
Warmup
SNVT
lev_percent
50
%
Warmup setting as a percent of maximum flow.
0
≤
range
≤
MaxFlowPos
Precision: 1
NightPurge
SNVT
lev_percent
50
%
Night purge setting as a percent of maximum flow.
0
≤
range
≤
MaxFlowPos
Precision: 1
WindowOpen
SNVT
lev_percent
0
%
Window open damper position. When a window is open, air flow
control is disabled, the flow damper is set to WindowOpenPos until
the space temperature drops below the temperature set point.
0
≤
range
≤
MaxFlowPos
Precision: 1
Table 23. Configuration Parameters (Continued)
NCI/Field
Net Data
Type
Default
Val
AP
Internal
Units
Description