ReheatCmd
lev_percent
Indicates the amount of modulating ReHeat that should be turned on in
the receiving nodes.
0
≤
range
≤
100%
TempFlowCmd
lev_percent
Output command of the temperature control loop in terms of percentage
(%) of flow capacity mapped to the minimum - maximum flow range (zero
percent as minimum flow and 100% as maximum flow).
0
≤
range
≤
100%
EffectOcc
occupancy
Effective occupancy
0: Occupied
1: Unoccupied
2: Bypass
3: Standby
PeriphStg
count_inc
Indicates the number of peripheral heat stages that should be turned on in
the receiving nodes
0
≤
range
≤
1
PeriphCmd
lev_percent
Indicates the amount of modulating peripheral heat that should be turned
on in the receiving nodes.
0
≤
range
≤
100%
nviSpaceCO2
ppm
ppm
Space CO2 concentration.
A valid input value overrides the local CO2 sensor.
0
≤
range
≤
5000 PPM
nviSpaceHum
lev_percent
%
Space relative humidity.
Typically used to override the local sensor value.
0
≤
range
≤
100%
nviSpaceTemp
temp_p
F
Network space temperature input. The network input overrides the local
temperature sensor.
14
≤
range
≤
122F
nviSupplyTemp
temp_p
F
Supply duct air input temperature.
This value is used for automatic heating and cooling mode changeover.
32
≤
range
≤
212 F
nviTodEvent
tod_event
This input network variable is used to command the Space Comfort
Controller into different occupancy modes. It is typically sent by a
scheduler or a supervisory node. If the network signal is valid, the network
overrides the local time schedule.
currentState
occupancy
Current scheduled state
0: Occupied
1: Unoccupied
3: Standby
255: null
nextState
occupancy
Next scheduled state
0: Occupied
1: Unoccupied
3: Standby
255: null
timeToNextState
minute
Time to next scheduled state.
0 to 65,534 minutes
Table 21. Network Variable - Inputs (Continued)
Nv/field
Net Data Type
SNVT
AP Internal
Units
Description