Manual ERS-BIC 160 kW V2.1
31
DC-L
I N K
The lines for connecting the DC intermediate circuit
from the AFEs to the HTS cabinet must be laid on the
left side of the AFE cabinet. Remove the acrylic cover
and place the cables with the markings A1-A4 on the
corresponding terminals and tighten the nuts with a
torque of 44
Nm. The cables to the HTS must be strain-
relieved on the rail below the fuses using the clamps
from the accessory pack (Reference No. 4a & 4b)!
N O T I C E
When connecting the cables to the DC bus, make
sure that the insulation plate of the HTS modules is
not damaged.
If cracks or kinks should occur here, the output stage
must not be energized!
Insulating plate
Abb. 22 Details on the HTS module/
Insulation plate
Fig. 21 Connection terminals DC inter-
mediate circuits
Rail for strain relief
Anschluss Sicherungshalter
Anschluss Sicherungshalter
Anschluss Sicherungshalter
Fuseholder terminals