HDG Bavaria GmbH 07/2008
HDG M299/300/350/400 - Version 1 - en
8 Troubleshooting – Possible faults
159
FA056
Flue gas
temperature
sensor is faulty
•
Flue gas temperature sensor
faulty
•
Line from flue gas
temperature sensor faulty
•
Check the flue gas
temperature sensor/line and
replace if necessary
FA057
Exhaust
temperature too
high
•
Flue gas temperature above
set maximum value
•
Press the
Acknowledge fault
key
FA058
Ash box full
•
Set monitoring time for ash
removal augers exceeded
•
Empty ash box
•
Reset time in the parameter
11-04
with
RESET
ST059
Boiler
temperature
sensor is faulty
•
Boiler temperature sensor
faulty
•
Line from boiler temperature
sensor faulty
•
Outlet on analogue module
faulty
•
Check the flue gas
temperature sensor/line and
replace if necessary
•
Check analogue module and
replace if necessary
FA065
Feed system
overfilling
•
The overfilling cover was
opened
•
Faulty limit switch
•
Connection cable faulty
•
Material blockage
•
Close overfilling cover
•
Check limit switch
•
Check the electrical
connection
•
Eliminate material blockage
FA066
Dosage
overfilling
•
The overfilling cover was
opened
•
Faulty limit switch
•
Connection cable faulty
•
Material blockage
•
Close overfilling cover
•
Check limit switch
•
Check the electrical
connection
•
Eliminate material blockage
FA067
Overfilling
Delivery system
•
The overfilling cover was
opened
•
Faulty limit switch
•
Connection cable faulty
•
Material blockage
•
Close overfilling cover
•
Check limit switch
•
Check the electrical
connection
•
Eliminate material blockage
FA068
Overfilling
Trough auger 2
•
The overfilling cover was
opened
•
Faulty limit switch
•
Connection cable faulty
•
Material blockage
•
Close overfilling cover
•
Check limit switch
•
Check the electrical
connection
•
Eliminate material blockage
FA069
Lateral auger
overfilling
•
The overfilling cover was
opened
•
Faulty limit switch
•
Connection cable faulty
•
Material blockage
•
Close overfilling cover
•
Check limit switch
•
Check the electrical
connection
•
Eliminate material blockage
No.
Fault
Cause
Remedy
Table 8/1 - Faults (continuation)
Содержание M299
Страница 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Страница 2: ......
Страница 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Страница 173: ...173 NOTICE ...
Страница 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Страница 175: ......