6 Using the heating system – SERVICE menu
114
HDG M299/300/350/400 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
– Fan + heating: The ignition fan switches on completely (fan +
heating).
✎
See “Procedure” in this section.
S
ETTING
VACUUM
PRESSURE
CONTROLLER
•
Negative pressure limit
If this set value is not met, the boiler switches to “Burn out”.
•
Positive pressure limit
If this set value is exceeded, the boiler is stopped as with an
“Emergency stop”.
•
Delay pressure control for grate
The response time of the pressure switch can be set.
•
Vacuum fan rotational speed uncontrolled
The constant rotational speed for an uncontrolled flue gas fan can be
set
✎
See “Procedure” in this section.
C
ALIBRATING
THE
LAMBDA
SENSOR
Ignition fan
5-08
1st filling
:
Off
Pre-ventilation :
Off
Heating up :
Off
END
Vacuum pressure control settings
5-09
Negative pressure limit
: -350 /-400 pa
Positive pressure limit :
0 /-400 pa
Delay press.control grate
:
5.0 /
0.0 m
Vacuum fan speed uncontr.
:
60 %
END
During the test procedure, do
not
close this submenu.
Duration: approx. 15 minutes!
The calibration of the lambda sensor can only be performed when
the heating system is in a cooled state and should be performed
once yearly.
The voltage of the lambda sensor must reach -7.0 mV within 15
minutes.
Содержание M299
Страница 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Страница 2: ......
Страница 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Страница 173: ...173 NOTICE ...
Страница 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Страница 175: ......