6 Using the heating system – SERVICE menu
108
HDG M299/300/350/400 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
•
30%
Starts the partial load measurement
•
100%
Starts the nominal load measurement
1.
Press the
F5
key under the display of the standard display screen.
✓
You are in the
SERVICE
menu.
✓
The display changes to the
Service 5-01
submenu.
2.
Press the
F4
key under the “Chimney sweep test” symbol.
✓
The display changes to the
Chimney sweep test 5-11
submenu.
3.
Press the
F3
or
F4
key to start the chimney sweep test.
✓
The chimney sweep test is carried out.
O
PERATING
HOURS
COUNTER
Various operating hours are displayed. Pressing the
RESET
key for
more than 3 seconds resets all operating hours.
1.
Open the
Service 5-02
submenu.
✎
See “Procedure” in this section.
2.
Using the
F1
key, select
service hour counter 11-01
in the
submenu.
Chimney sweep mode
5-11
Burn out
Enable boiler temperature :
75 / 0 °C
Enable comb. chamb. temp. :
450 / 0 °C
Measurement duration :
75 / 0 m
30%
100%
END
Counter operating hours
11-01
Boiler
:
0:00:00
Dosage : 0:00:00
Feeding : 0:00:00
Ash removal : 0:00:00
RESET
END