6 Using the heating system – SERVICE menu
121
5.
You are now in the
Output control 6-01
submenu.
E
NTERING
FUEL
AND
TEMPERATURE
SETTINGS
In this menu, you can define the fuel quantity for controlled
operation of the boiler.
✎
See “Procedure” in this section.
E
NTERING
THE
PRIMARY
AIR
SETTING
In this menu, you can set the primary air quantity for controlled
operation of the boiler.
✎
See “Procedure” in this section.
The fuel settings apply for
Combustion control
as well as
Combustion and output control
.
✎
See section “6.6 ON/OFF menu”, under “Setting the control,
boiler activation and Lambda Stop”.
Material controller
6-02
Max: 50.0%
Output_Set:100.0 %
Min: 10.0%
Material_Set: 50.0 %
END
The difference between fuel quantity
MAX
and
MIN
should be
specified as a range (approx. 25%) adapting to the required value.
The primary air settings apply for
Combustion control
as well
as
Combustion and output control
.
✎
See section “6.6 ON/OFF menu”, under “Setting the control,
boiler activation and Lambda Stop”.
Primary air fan
6-04
Air_Max
: 35%
Fuel_SET : 50.0%
Air_MIN
: 25% Air_SET : 30 %