6 Using the heating system – SERVICE menu
115
1.
Open the
SERVICE
menu and scroll to the
Service 5-02
submenu.
✎
See “Procedure” in this section.
2.
Simultaneously press the keys
F3
,
F4
and
F5
under the display.
3.
Press the F2 key and scroll to the
Service 5-10
submenu.
✓
The test mode
Off
message is shown in black.
4.
Press the
F3
key to start the lambda sensor test.
✓
The calibration of the lambda sensor begins; the message
-ON-
appears in the display. The minute counter starts running. The
lambda sensor heater switches on, the main fan starts and the
secondary air supply opens.
If the voltage of -7.0 mV is reached after 15 minutes, the lambda
sensor test has been successfully completed.
✓
The testing of the lambda sensor is completed.
5.
Press the
F6
key under the
END
command to exit the
Service
5-07
submenu.
✓
The standard display is restored.
C
HIMNEY
SWEEP
TEST
•
Enabling boiler temperature
After this set boiler temperature is exceeded, the chimney sweep test
is enabled.
•
Enabling combustion chamber temperature
After this set combustion chamber temperature is exceeded, the
chimney sweep test is enabled.
•
Boiler set temperature 30/100%
The boiler set temperature for the chimney sweep test in partial load
(30%) and nominal load (100%) can be set.
Service
5-10
Lambda sensor test
:
: -Off-
Lambda setpoint 21.0% :
12.8 % : / .0 mV
Test time 15 minutes :
00.0 m
Start
Stop
END
Содержание M299
Страница 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Страница 2: ......
Страница 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Страница 173: ...173 NOTICE ...
Страница 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Страница 175: ......