4 Planning and installation – Structural requirements
32
4.2 Structural requirements
R
EQUIRED
ROOM
SIZES
AND
MINIMUM
CLEARANCES
B
OILER
INSTALLATION
SITE
/
BOILER
ROOM
B
OILER
INSTALLATION
SITE
Heating systems for solid fuels with a nominal thermal power of up to
50 kW may be installed in a boiler room.
B
OILER
ROOM
Boilers for solid fuels with a nominal thermal power of more than 50
kW may only be installed in special boiler rooms.
A
PPLICABLE
REGULATIONS
Local building regulations always apply. In Germany, individual state
regulations on boilers and furnaces (FeuVO) also apply.
Figure 4/3 - Required room sizes and minimum clearances
C
F
B
D
A
E
A
B
C
D
E
F
Minimum
room
height
Recom-
mended
room
height
HDG Compact 25/35
2900
700
1800
400
700
1200
1950
2250
HDG Compact 45/50/65
2900
800
2000
400
700
1200
2250
2500
HDG Compact 80
3150
800
2000
400
700
1200
2450
2750
Table 4/3 - Minimum size (mm)