S
M1
S1
M2
S2
M3
S3
S
S
S
Boundary clock
switch
Transparant clock
switch
Grand master
clock
M
Grand master
clock
M
Boundary clock operation
Transparent clock operation
System 1
System 2
System 3
System 1
System 2
System 3
Figure 14.1:
Boundary clock versus transparent clock switch synchronization
mode
14.2.1
Switches using boundary clocks
Switches using boundary clocks have a built
-
in clock and they create separate
synchronization domains by segmenting the synchronization path from the
master clock to several slave clocks. As a result, systems downstream of a
boundary clock do not communicate PTP messages with the selected (grand)
master directly. Standard Ethernet messages are passed through the switch
while synchronization messages are used to synchronize the boundary slave
clock.
HINT/TIP
As boundary clock switches create their own internal clock, the overall stability
and/or accuracy of the grandmaster clock is no longer available for any of the
attached systems.
GEN3i
I3763-3.1 en HBM: public
321
Содержание GEN3i
Страница 1: ...Portable Data Recorder GEN3i English User Manual I3763 3 1 en HBM public...
Страница 4: ...4 I3763 3 1 en HBM public...
Страница 51: ...33 46 7 70 IEC 61010 1 2010 IEC EN 50110 1 EN 50110 2 50 120 GEN3i I3763 3 1 en HBM public 51...
Страница 119: ...Figure 8 2 Acquistion control Detail A Record B Stop C Pause D Trigger GEN3i I3763 3 1 en HBM public 119...
Страница 822: ...Once the computer name has been entered correctly click Next Figure E 14 Computer name GEN3i 822 I3763 3 1 en HBM public...
Страница 1158: ...1158 I3763 3 1 en HBM public...
Страница 1159: ......