AD104-R2, AD104-R5
63 / 75
ba_aed104_8_e.doc
7.6
Bus termination for RS-485 version
STR
Set Termination Resistor
(Bus termination resistors)
Range:
0/1
Factory setting:
0 (off)
Response time:
<15ms
Parameters:
1
Password protection:
none
Parameter protect.:
with command
TDD1
Query:
STR?
Effect:
0/1 crlf
Befehl:
STR0/1;
Effect:
0 = Bus termination switched off
1 = Bus termination switched on
The necessary measures for the electrical bus termination (resistors) were described in Section 5.3. These
resistors protect the zero-signal level on the master line if none of the connected modules is transmitting.
Observe here that this bus termination must be switched on only twice per bus system (master line), and is
generally located at the line ends of the master line.
Normally the interface of the master contains such a bus termination and the termination is switched on at the
most remote AED via the command
STR1;.