TSA 160 NT
50
Service menu
Designation
Setting values
Explanation
Closing position GF
NO
Closing position contact of the door leaf
à
For 1-leaf Door
à
For 1-leaf Door drive with manual passive
leaf (door closer):
Closing position contact of the active leaf
à
For 2-leaf door:
Active leaf contact to GF control, passive leaf
contact to SF control
Emergency lock
20kOhm
NO
The input can be used to connect an emergency
lock switch.
When the emergency lock switch is activated, the
contact is closed and 17.83 V is applied to the input.
The door closes and locks.
The contact sensors KI, KA and KB are blanked.
The door remains closed as long as the emergency
lock signal is applied to the input.
P-KI activation
NO
Additional contact sensor (P-KI, P-KA). For con-
nection of additional closing contacts.
P-KA activation
NO
Switch function
NO
With 2-leaf assemblies the push button can be
connected to the active leaf control or to the
passive leaf control.
When the push button is pressed once, the
drive opens the door. When the push button is
pressed again, the drive closes the door.
If the push button is connected to the passive
leaf control opening and closing when both door
leaves are activated if the internal programme
switch of the passive leaf control is set to AUT.
Switch function hold-
open time (OHZ)
NO
With 2-leaf assemblies the push button can be
connected to the active leaf control or to the
passive leaf control. When the push button is
pressed once, the drive opens the door and
closes after the hold-open time has expired.
When the push button is pressed again (within
the hold-open time) the drive closes the door
without waiting for the hold-open time to expire.
If the push button is connected to the active
leaf, the 1-leaf hold-open time is used for 1-leaf
use and the 2-leaf hold-open time for 2-leaf use.
Stop 1.2 kOhm
For the connection of a stop push button with
1.2 kOhm terminating resistor.
Reset switch
NO
For restarting the drive.
Function as reset.
Double push button NO
1 × press = 1-leaf Open
2 × press = 2-leaf Open
Stop normally opened
contact
NO
For connection of a stop push button.
Stop normally closed
contact
NC
PS-NA
NO
Night mode programme
PS-LS
NO
Exit only programme
Closed position SF
NO
SF or door closer closed
Stop 2.0 kOhm
NO
For the connection of a stop push button with
2.0 kOhm terminating resistor.
Protection in accordance with EN 16005/DIN 18650.
WC control
NO
with IO 420
1-leaf opening
NO
Only on the active leaf (2-leaf drive)
OFF normally closed
contact
NC
Switchover to OFF (electric strike)