TSA 160 NT
29
Electric strike
GEZE electric strike for fire protection doors
GEZE electric strike type Mat. no. Current consumption Voltage
Functions
FT500--B
144634 200 mA (at 12 V)
100 mA (at 24 V)
Continuous operation: 12 or 24 V DC ±15 %
Momentary operation: 12–48 V AC/DC
Fail-secure electric strike,
fire protection doors
FT501--E
with switch contact
144647 200 mA (with 8–11 V)
50 mA (with 12-24 V)
Continuous operation: 8–28 V DC
Momentary operation: 8-28 V AC/DC
Fail-secure electric strike,
fire protection doors,
opening under sideload
with direct voltage
à
Max. current consumption of 1000 mA, but pay attention
to the total current consumption of all the components,
especially for fail-safe electric strikes.
à
Fail-secure electric strikes for TSA 160 NT:
à
IQ eStrike A5000--E, mat. no. 145182
à
Fail-safe electric strikes for TSA 160 NT:
à
IQ eStrike A5300--B, mat. no. 144631
X
Mount a free-wheeling diode 1N4007 (1), mat. no. 115293
(no free swing diode is required for GEZE electric strike).
1
2
GND
1
2
24V
31
TOEA
32
TOEB
TOE
RM
33
1
Free swing diode
2
Wire jumper
12.2 Customer-supplied 12 V AC electric strike
Contact load output TOE with 12 V AC: max. 1 A
~ 12V AC ~
max. 1A
GND
1
2
24V
31 TOEA
32 TOEB
TOE
RM
33
12.3 Bar message
à
Input RM blocks the activation of the drive when the door is locked. If the Input RM becomes active while
the door is open, the door reverses and remains open.
à
If a further electric strike is connected with
à
Normally opened contact: Circuit the contacts in parallel.
à
Normally closed contact: Switch the contacts in series.
à
Setting the parameters:
à
DPS:
Set
®®
to
01
(normally opened contact) or
0 2
(normally closed contact).
à
ST220: Set the “Signals”, “Input signals”, “Bolt contact type”, “Bolt contact type” to “ normally opened
contact contact ” or “normally closed contact”.
à
S1, S2: Set parameter 21 to value 01 (normally opened contact) or 02 (normally closed contact).
GND
1
2
24V
31
TOEA
32
TOEB
TOE
RM
33
GND
1
2
24V
31
TOEA
32
TOEB
TOE
RM
33
Normally opened contact
Normally closed contact