TSA 160 NT
35
Motor, solenoid valve
16 Motor, solenoid valve
à
TSA 160 NT EN3-6
à
Hydraulic unit, mat. no. 019603
à
Motor capacitor, mat. no. 058821
à
1~ motor, 220-230 V, 1.10 A, 50 Hz
cos phi 0.98, 0.125 kW, S2-6 Min.,
WSK 140 °C, C 8 µF, 400 V DB, IP44, EN60034
1
Solenoid valve
2
Solenoid valve 24 V/160 mA
17 Limit switch
17.1 Open position
TSA 160 NT
X
Set the blue cam so that the limit switch is
operated in the open position of the door.
TSA 160 NT Invers
X
Set the blue cam so that the limit switch is
operated in the closing position of the door.
To take the strain off the lock latch, a motor run-
on time HL (0 s … 5 s) can be set, during which
the motor presses the door leaf further into the
closing position.
1 Yellow cam:
Wall blanking SIO
2 Blue cam:
TSA 160 NT Open position
TSA 160 NT Invers closing position
Setting the parameters:
à
DPS: Set
hl
to the required motor run-on time.
à
ST220: Set “Movement parameters”, “Motor run-on time” to the required run-on time.
à
S1, S2: Set parameter 23 (HL) to the required motor run-on time.
17.2 Wall blanking SIO
X
If the door moves towards a wall when opened, set the yellow cam so that the SIO is blanked (skipped) before
the wall is detected.
à
The yellow cam can be used for monitoring the closing position if the wall blanking function is not required.