TSA 160 NT
16
Safety sensor open and close
5.3.4 GC 334 connection over interface GC 334
The GC 334 interface is used to connect a customer's existing cable transition.
1 GND
13 SIO
10 TST
2 24V
SIO
4
3
2
5
1
11 SIS
SIS
-
+
-
+
60mA
6
4
5
1
2
3
1
1
GC 334 module
2
Opposite hinge side
3
Hinge side
4
GC 334 hinge side
5
Interface GC 334
6
Door transmission cable
5.4 Safety sensor GC 335
X
Follow the installation instructions.
X
Use the reference body, mat no. 120190, to set the detection area.
X
Always install the master module near the hinge, connection with drive control takes place at the master module.
X
Connect max. 7 slave modules to one master module.
X
Open the configuration bridge at the last slave module or at the master module (if no slave modules connected).
X
Setting the “Testing” parameter.
à
DPS: Set
Te
to
01
(testing with 24 V).
à
ST220: Set “Output signals”, “Testing SI” to “Testing with 24V”.
à
S1, S2: Set parameter 11 to 01 “Testing with 24 V”.