TSA 160 NT
41
Commissioning and service
X
Switch the mains supply voltage off.
X
Re-establish the RS485 connection active leaf control – passive leaf control.
X
Switch the mains supply voltage on again.
X
With TSA 160NT F: Press the reset switch.
Separate parameter setting for the controls is no longer necessary.
The drive for which parameter setting is to take place (GF or SF) can be selected via the service terminal.
X
Set further parameters, in particular:
à
“Door parameters”: “Number of leaves”, “Drive type”, “Type of installation”, “Type of electric strike”
à
“Input signals”: “SI1 contact type”, „SI1 function”, “SI3 contact type”, “SI3 function”, “Bolt contact type”, “AU
contact type”
à
“Output signals”: “Testing SI”
If all contact of the door leaf with persons is to be avoided, safety sensors for monitoring opening and closing
have to be mounted in accordance with DIN 18650 and be tested by the control.
X
Check the running behaviour of the door and adjust other parameters if necessary.
Clear the fault memory of the controls:
X
Select the control via “Active leaf Para” or “Passive Leaf Para” respectively:
X
Use “Diagnosis”, “Fault memory”, “Clear current faults”, “Yes” and “Clear old faults” – “Yes” to clear the fault
memory of the selected control.
X
Unplug ST220.
The installation is complete (see installation instructions of the corresponding swing door drive).
Sensors are correctly configured and aligned.
X
Clear the detection area of the sensors.
Electrical installation is complete.
21.2.3 Commissioning with DPS
Configuring a brand-new 2-leaf drive
X
Switch the mains supply voltage off.
X
Set the internal programme switch to “II AUT”.
X
Disconnect the RS485 connection active leaf control – passive leaf control.
X
Connect DPS with the active leaf control.
X
Switch the mains voltage supply on.
X
With TSA 160 NT F press the reset switch.
X
Open the Service menu by pressing the hidden service push button and the ENTER push button (exit only) at
the same time.
X
Change parameter
ef
from “
0 0
” (1-leaf drive) to
01
(2-leaf active).
X
Set further parameters on the active leaf control, in particular:
à
Set
ef
(Number of leaves),
a T
(Drive type),
ht
(Type of installation),
TO
(Type of electric strike),
si
(SI1 contact
type),
fi
(SI1 function),
s3
(SI3 contact type),
f3
(SI3 function),
®®
(Bolt contact type),
ps
(AU contact type),
Te
(Testing SI)
X
Exit the service menu.
X
Set the internal programme switch on the passive leaf drive to “II AUT”.
X
Connect DPS with the passive leaf control and open the Service menu via DPS.
X
Change parameter
ef
from
0 0
(1-leaf drive) to
0 2
(2-leaf passive)
X
Set further parameters on the passive leaf control, in particular:
à
Set
ef
(Number of leaves),
a T
(Drive type),
ht
(Type of installation),
TO
(Type of electric strike),
si
(SI1 contact
type),
fi
(SI1 function),
s3
(SI3 contact type),
f3
(SI3 function),
®®
(Bolt contact type),
ps
(AU contact type),
Te
(Testing SI)
X
Exit the Service menu by pressing the hidden Service push button and the push button x (night mode) at the same time.
X
Switch off the mains power supply of the drive.
X
Disconnect DPS from the control again.
X
Set up RS485 connection active leaf/passive leaf control again (connector RS485/ASF or connector RS485).
X
Switch on the mains voltage.
X
For TSA 160 NT F: Press the reset switch.
If all contact of the door leaf with persons is to be avoided, safety sensors for monitoring opening and closing
have to be mounted in accordance with DIN 18650 and be tested by the control.