TSA 160 NT
42
Commissioning and service
21.2.4 Commissioning via service push buttons S1 and S2.
Configuring a brand-new drive
For 2-leaf drives, the RS485 connection can be maintained between active leaf and passive leaf control.
The parameters are set directly at the respective control via the Service push buttons.
Active leaf drive:
X
1-leaf drive: Set parameter “01” (Number of leaves) to “00” (1-leaf drive) (factory setting).
X
2-leaf drive: Change parameter “01“ (Number of leaves) from “00” (1-leaf drive) to “01 “(2-leaf active).
X
Set further parameters on the active leaf control, in particular:
à
“29” (Drive type), “27” (Type of installation), “20” (Type of electric strike), “07” (SI1 contact type), “08” (SI1
function), “09” (SI3 contact type), “10” (SI3 function), “21” (Bolt contact type), “11” (Testing SI)
Passive leaf drive:
X
Change parameter “01“ (Number of leaves) from “00” (1-leaf drive) to “02 “(2-leaf passive).
X
Set further parameters on the passive leaf control, in particular:
à
“29” (Drive type), “27” (Type of installation), “20” (Type of electric strike), “07” (SI1 contact type), “08” (SI1
function), “09” (SI3 contact type), “10” (SI3 function), “21” (Bolt contact type), “11” (Testing SI)
21.3 Finish commissioning
X
Switch off the mains power supply of the drive.
X
Reverse the hold-open of the active leaf in the open position.
X
Switch on the mains power supply of the drive.
X
With TSA 160 NT F press the reset switch.
X
Check function and detection areas of all contact sensors.
X
Check the function and detection areas of the safety sensors for monitoring closing and opening.
At sensor strips:
X
Check each individual sensor module.
X
Check the angle of the hiding of the safety sensor open and if necessary correct the setting of the limit switch
wall blanking.
X
If necessary correct the settings of the limit switch (open position/close position).
21.4 Changing the parameters of a 2-leaf drive
Parameter S1, S2
DPS
ST220
Description
1
ef
Number of leaves
Active leaf/passive leaf
7
s1
Safety 1 contact type
8
f1
Safety 1 function
9
s3
Safety 3 contact type
10
f3
Safety 3 function
11
Te
Testing
Testing safety sensors
20
TO
Electric strike type
Selection of the electric strike
21
®®
Bar message
Contact for bar message
19
ps
Automatic contact type
Selection of function Au input
29
a T
Drive type
27
h T
Type of installation
Stop type