TSA 160 NT
13
Safety sensor open and close
5.2.2 Monitoring opening
2
1
SIO
13
1
GND
2
24V
10 TST
SIO
-UB
+UB
COM
+
SIO
60 mA
Test
SIS
BN
GN
YE
WH
PK
GY
BU
RD
1
GC 342 hinge side
2
Door transmission cable
Settings DCU5
X
Setting the contact type parameter:
à
DPS:
Set
s3
to
0 2
(normally closed contact) (factory setting).
à
ST220: Set the “Input signals”, “SI3 – terminal SIO”, “SI3 contact type” to “normally closed contact” (factory setting).
à
S1, S2: Set parameter 9 to 02 “normally closed contact”.
X
Setting the function parameter:
à
DPS: Set
f3
to
0 5
(SIO stop) or
0 6
(SIO stop SF GF).
à
ST220: Set the “Input signals”, “SI3 – terminal SIO”, “SI3 function” to “SIO stop” or “SIO stop SF GF”.
à
S1, S2: Set parameter 10 to 05 “SIO Stop” or 06 (SIO stop SF GF).
5.2.3 Monitoring closing
2
1
SIS
11
1
GND
2
24V
10 TST
SIS
-UB
+UB
COM
+
SIO
60 mA
Test
SIS
BN
GN
YE
WH
PK
GY
BU
RD
1
GC 342 opposite hinge side
2
Door transmission cable
Settings DCU5
X
Setting the contact type parameter:
à
DPS:
Set
s1
to
0 2
(normally closed contact) (factory setting).
à
ST220: Set the “Input signals”, “SI1 – terminal SIS”, “SI1 contact type” to “normally closed contact” (factory setting).
à
S1, S2: Set parameter 7 to 02 “normally closed contact”.
X
Setting the function parameter:
à
DPS: Set
f1
to the desired function.
à
ST220: Set the “Input signals”, “SI1 – terminal SIS”, “SI1 function” to the desired function.
à
S1, S2: Set parameter 8 to the desired function.
Содержание TSA 160 NT F
Страница 61: ...TSA 160 NT 61 Fault messages ...
Страница 62: ...TSA 160 NT 62 Fault messages ...
Страница 63: ...TSA 160 NT 63 Fault messages ...