TSA 160 NT
9
Safety sensor open and close
5
Safety sensor open and close
X
In the case of 2-leaf systems connect the safety sensors of the active leaf with the active leaf control and those
of the passive leaf with the passive leaf control.
X
Install the sensor for monitoring closing on the door leaf, opposite hinge side.
The sensor for monitoring closing can also be used as a contact sensor outside or inside.
X
Setting the parameters:
à
DPS: Set
f1
to
0 2
(“SIS and KI”) or
0 3
(“SIS and KA”).
à
ST220: Set “Signals”, “Input signals”, “SI1 – terminal SIS”, “SI1 function” to “SIS and KA” or to “SIS and KI”.
à
S1, S2: Set parameter 8 to 02 (“SIS and KI”) or 03 (“SIS and KA”).
If the SIS is activated during closing, the door reverses and opens again.
à
TSA 160 NT:
à
If a closing position limit switch is connected, the SIS is blanked as soon as the closing position is reached
(see chapter 11, “Configurable inputs”, “Closing position limit switch”).
à
Without closing position limit switch the SIS is only blanked 10 s after the closing process starts. If the SIS is
activated within this time, the door opens.
à
TSA 160 NT Invers:
à
The SIS is blanked directly after the closing position has been reached.
X
Install the sensor for monitoring opening on the door leaf, hinge side.
à
If the SIO is activated during opening, the door stops.
à
At detection the sensor output is open (0 V applied to SIS or SIO input).
à
2-leaf doors:
à
Both door leaves stop when one of the two SIO sensors is activated, if the function “SIO Stop SF GF” is set in
the configuration for the safety sensor open (SIO).
X
Check function and correct setting of the sensors during commissioning and service.
To operate the display programme switch DPS see chapter 24.1, “Display programme switch (DPS)”.
To operate the service terminal ST220 see chapter 23.2, “Operation of ST220”.
5.1 Safety sensor GC 338
X
Follow installation instructions GC 338.
à
Accessories:
à
Spot finder( mat. no. 112321)
The connector plug of the GC 338 has 6 poles. Terminal 6 is not occupied.
X
Set DIP switch 3 (TST/SBY) on the GC 338 interface module to ON (factory setting).
X
Setting the testing parameter:
à
DPS: Set
Te
to
01
(testing with 24 V).
à
ST220: Set “Output signals”, “Testing SI” to “Testing with 24 V”.
à
S1, S2: Set parameter 11 to 01 “Testing with 24 V”.