TSA 160 NT
28
Electric strike
12 Electric strike
X
Connect the electric strike of the active leaf to the active leaf control and the electric strike of the passive leaf
to the passive leaf control.
à
Floating relay contact, switching voltage/current max. 24 V AC/DC, 1 A.
à
Activation of the electric strike is limited to 5 s plus the activation delay time by parameters
D l
.
X
In case of an TSA 160 NT Invers use only emergency exit electric strikes, holding magnet or GEZE motor lock
GEZE IQ Lock EL.
à
Set the parameter electric strike type with:
à
DPS: Set
TO
to the desired electric strike type (see Service menu DPS).
à
ST220: Set the “Door parameters”, “Electric strike type” to the required type (see chapter 24.3, “DPS ser-
vice menu and service buttons S1/S2 with LEDs”).
à
S1, S2: Set parameter 20 to the desired electric strike type.
à
Holding magnet MA 500 with counter plate, mat. no. 024740, for the magnetic locking of emergency exit doors.
à
Motor lock with panic function GEZE IQ Lock EL for 1-leaf doors.
The GEZE IQ Lock EL is a self-locking anti-panic motor lock with external control.
See wiring diagram for motor lock IQ Lock EL.
IQ Lock SecuLogic set
(Motor lock PZ-bored, complete, incl. flat face plate and strike plate, motor lock control, power supply cable for
control, reed switch contact as well as open drip loop)
Designation
Distance
Backset
Mat. no.
IQ Lock EL 9235
92
35
103601
IQ Lock EL 9240
92
40
115013
IQ Lock EL 9245
92
45
103699
IQ Lock EL 7255
72
55
103700
IQ Lock EL 7265
72
65
103701
IQ Lock EL 7280
72
80
106571
IQ Lock EL 7210
72
100
106572
à
When a motor lock without feedback is used, a closing position limit switch is necessary (see chapter 11.10,
“Closing position monitoring, closing position blanking SIS, Push And Go”). An activation delay must be set
using parameter dL (“Opening delay) which gives the motor lock time to unlock.
à
Set the parameter
D l
(“Opening delay”) with:
à
DPS: Set
D l
to the necessary time (00 ... 20 s).
à
ST220: Set the “Door parameters”, “Opening delay” to the required time.
à
S1, S2: Set parameter 22 to the required time (00 … 20).
12.1 24V DC electric strike supplied on drive side
GEZE electric strikes for standard applications, doors with access control
GEZE electric strike type Mat. no. Current consumption Voltage
Functions
A5000--B
144590 200 mA (at 12 V)
100 mA (at 24 V)
Continuous operation: 12 or 24 V DC ±15 %
Momentary operation: 12–48 V AC/DC
Fail-secure electric strike,
standard applications, doors
with access control
A5000-FB
with lock latch guide
144632 200 mA (at 12 V)
100 mA (at 24 V)
Continuous operation: 12 or 24 V DC ±15 %
Momentary operation: 12–48 V AC/DC
Fail-secure electric strike,
standard applications, doors
with access control
A5300--B
144631 200 mA (at 12 V)
100 mA (at 24 V)
Continuous operation: 12 or 24 V DC ±15 % Fail-safe electric strike,
standard applications
A5000--E
145182 200 mA (with 8–11 V)
50 mA (with 12–24 V)
Continuous operation: 8–28 V DC
Momentary operation: 8-28 V AC/DC
Fail-secure electric strike,
standard applications,
opening under sideload
with direct voltage
A5001--B
with switch contact
145183 200 mA (at 12 V)
100 mA (at 24 V)
Continuous operation: 12 or 24 V DC ±15 %
Momentary operation: 12–48 V AC/DC
Fail-secure electric strike,
standard applications, doors
with access control