2900 FIREGUARD

®

 Electromechanical Closer-Holder Device Models

12-2960, 9-2960 and 2960 Multipoint Hold Open with Rigid Arms    

Pull (Hinge) Side Installation Instructions

CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE 

For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com 

A7395C

1

FOR MODELS 12-2960 / 9-2960 / 2960

1. Use dimensions shown on page 5 provided to locate

  attaching screws on frame and door. Prepare holes

 

  For concealed wire applications only

  Locate and drill 1-1/8" diameter hole in the frame face for

  3/4" conduit. (This is normally done at the time the frame

  is being installed.) Connect conduit to backplate before 

  fastening backplate to frame

2. Attach backplate/closer assembly to frame. Position backplate

  end with terminal strips away from hinge edge of frame

 

3. Make electrical connections:

  A) 12-2960: Select and follow the wiring diagram from wiring

  instructions sheet A7408 and 'Checkout Procedure' from Page 3.

  B) 9-2960: Make solenoid wire connections with power input wires 

  from 12-2960 using two wire nuts provided in screw pack.  Select 

  proper wiring diagram and 'Checkout Procedure' from Page 3.

4. Make input power connections to the power supply board as directed. 

  NOTE: If electrical connections are to be made at a later date, 

  place cover on chassis now to prevent its loss, see Step F.

5. Installation of arm on closer: With appropriate size wrench, rotate

  closer top spindle approximately 45

ϒ

 (see step C below) (NOTE: 

  Closing both valves for door speed and latching speed makes this 

  procedure much easier). Position closer arm on bottom spindle 

  approximately parallel to the door and arm length away from hinge. 

  Secure arm with screw and washer

 

6. Installation of track on door: Remove end cap from track. Position

  track with open side up. Insert roller end of closer arm in sliding

  groove of track. With arm engaged in slide groove, slide track, into

  position so that prepared holes on door align with track holes

  Replace end cap and secure track to door

B

12-2960

2960

Backplate

Screw (6)

Backplate

Closer/Holder

Closer

Screw (4)

Smoke

Detector

Conduit Nut

(By others)

On/Off

Switch

Terminal

Strips

Terminal

Strips

3/4" Conduit

(By others)

Track Screw

(2 Reqd)

Track

Rigid Arm

9-2960

Companion unit (without electronics) not shown

Position of Arms and Index Settings

C

Right Hand Door

Index

Mark on

Spindle

View Looking Up When

Assembling Arm to Spindle

View Looking Up When

Assembling Arm to Spindle

Left Hand Door

Index

Mark on

Spindle

Approximate

Preload

Position of Main Arm

When Assembled to Spindle

MODEL

12-2960

NOTE:

Devices are handed

and must be the same

hand as door.

RH - Right Hand Door

LHR - Left hand Reverse

LH - Left Hand Door

RHR - Right Hand Reverse 

MODELS

2960/9-2960

A7395C.indd   1

10/29/18   12:44 PM

Содержание Fireguard 2900 Series

Страница 1: ...ater date place cover on chassis now to prevent its loss see Step F 5 Installation of arm on closer With appropriate size wrench rotate closer top spindle approximately 45ϒ see step C below NOTE Closing both valves for door speed and latching speed makes this procedure much easier Position closer arm on bottom spindle approximately parallel to the door and arm length away from hinge Secure arm wit...

Страница 2: ...g and latching speeds Turn valves clockwise to slow down or counterclockwise to speed up door movement Backcheck To regulate the intensity of backcheck action turn valve clockwise to increase or counterclockwise to decrease checking Caution Set valve for slight cushioning effect Closer can be damaged if the checking action is too abrupt Never use the backcheck as a door stop Always use a door stop...

Страница 3: ...s On Off Switch Door should close and latch Adjustment of spring power may be necessary to ensure proper latching Depress on off switch again Open door to hold open position door will hold open 3 ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL ELECTRICAL CODES ORDINANCES AND REGULATIONS 4 MAXIMUM WIRE SIZE IS 18AWG CAUTION Input power supply must match circuit board voltage rating either 24VAC DC or ...

Страница 4: ... a feature that detects when a smoke sensing chamber requires cleaning due to dirt and dust The need for cleaning is indicated by the flashing of the Red LED light once per second Normal Supervisory Operation Red LED flashes once every 8 seconds Dirty Chamber needs cleaning Red LED flashes once every second Smoke Detection Red LED is continuously illuminated To clean the smoke detector assembly fo...

Страница 5: ...A7395C 5 A7395C indd 5 10 29 18 12 44 PM ...

Страница 6: ...A7395C 6 FIREGUARD A7395C indd 6 10 29 18 12 44 PM ...

Отзывы: