A7395C

2

1/8” HEX SOCKET 

WRENCH

BACKCHECK 

RANGE

CLOSING SPEED 

RANGE

LATCHING SPEED 

RANGE

Adjust Spring Power According to Chart

Turn the spring adjusting nut clockwise the required number of turns to match door width as indicated in chart. Where strong drafts exist, increase spring power

as needed. 351 Series door closers leave the factory with the spring adjustment set at eight (8) turns

D

Clockwise Turns

of Adjusting Nut

8
8

12
16

Maximum adjustment is

approximately 20 turns.

Do not forcibly extend

adjustment beyond limits.

5/8 " Adjustment Nut

Adjustment Instructions

E

Minimum recommended door closing time is 6 seconds for doors opened to 90 degrees.

  

Use 1/8" hex (Allen) wrench to adjust valves as needed.

Closing and latching speeds:

Turn valves clockwise to slow down or counterclockwise to speed up door movement.

Backcheck:

To regulate the intensity of backcheck action, turn valve clockwise to increase or counterclockwise to decrease checking.

Caution: Set valve for slight cushioning effect. Closer can be damaged if the checking action is too abrupt. Never use the backcheck 

as a door stop. Always use a door stop to stop the door.

Backcheck

valve

Closing 

speed

valve

Latching 

speed

valve

9-2960 Without Electronics not shown

2960

1.  Assemble (3) short cover screws

  (#8-32 x 5/16") into bottom of

  closer body and cover mounting

  bracket, approx. one turn

CAUTION:

 Avoid

interference with

electronics and wires

during installation of cover

2.  Slide cover onto backplate and

  closer assembly. Secure with

  three cover screws

Adjust closers as directed

in steps D and E

To Install Cover

F

12-2960

On/Off

Switch

A7395C.indd   2

10/29/18   12:44 PM

Содержание Fireguard 2900 Series

Страница 1: ...ater date place cover on chassis now to prevent its loss see Step F 5 Installation of arm on closer With appropriate size wrench rotate closer top spindle approximately 45ϒ see step C below NOTE Closing both valves for door speed and latching speed makes this procedure much easier Position closer arm on bottom spindle approximately parallel to the door and arm length away from hinge Secure arm wit...

Страница 2: ...g and latching speeds Turn valves clockwise to slow down or counterclockwise to speed up door movement Backcheck To regulate the intensity of backcheck action turn valve clockwise to increase or counterclockwise to decrease checking Caution Set valve for slight cushioning effect Closer can be damaged if the checking action is too abrupt Never use the backcheck as a door stop Always use a door stop...

Страница 3: ...s On Off Switch Door should close and latch Adjustment of spring power may be necessary to ensure proper latching Depress on off switch again Open door to hold open position door will hold open 3 ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL ELECTRICAL CODES ORDINANCES AND REGULATIONS 4 MAXIMUM WIRE SIZE IS 18AWG CAUTION Input power supply must match circuit board voltage rating either 24VAC DC or ...

Страница 4: ... a feature that detects when a smoke sensing chamber requires cleaning due to dirt and dust The need for cleaning is indicated by the flashing of the Red LED light once per second Normal Supervisory Operation Red LED flashes once every 8 seconds Dirty Chamber needs cleaning Red LED flashes once every second Smoke Detection Red LED is continuously illuminated To clean the smoke detector assembly fo...

Страница 5: ...A7395C 5 A7395C indd 5 10 29 18 12 44 PM ...

Страница 6: ...A7395C 6 FIREGUARD A7395C indd 6 10 29 18 12 44 PM ...

Отзывы: