5-236
L90 Line Current Differential System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
The element resets instantaneously. The minimum voltage setting selects the operating voltage below which the element is
blocked.
Figure 5–124: AUXILIARY UNDERVOLTAGE SCHEME LOGIC
f) AUXILIARY OVERVOLTAGE
(ANSI 59X, IEC PTOV)
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
VOLTAGE ELEMENTS
AUXILIARY OV1(2)
The L90 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under
SYSTEM
SETUP
AC INPUTS
VOLTAGE BANK X5
AUXILIARY VT X5 SECONDARY
is the per-unit (pu) base used when setting the
pickup level.
A typical application for this element is monitoring the zero-sequence voltage (3V_0) supplied from an open-corner-delta
VT connection.
AUXILIARY OV1
AUX OV1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
AUX OV1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
AUX OV1 PICKUP:
0.300 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
AUX OV1 PICKUP
DELAY: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
AUX OV1 RESET
DELAY: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
AUX OV1 BLOCK:
Off
Range: FlexLogic operand
MESSAGE
AUX OV1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
AUX OV1 EVENTS:
Disabled
Range: Disabled, Enabled
REV
DATE
ECO#
DWN APP
DESCRIPTION
THIS DRAWING IS PROPRIETARY INFORMATION
DRAWN BY/DATE:
ENG. APP./DATE:
MFG. APP./DATE:
SCALE:
DWG. SIZE: B
DWG. No.:
PART No.:
REV.
DWG. No.
WHERE USED
PARTS LIST No.
LOGIC DIAGRAM,
UR SERIES,
AUXILIARY UNDERVOLTAGE ELEMENT
N/A
A2
BA/04/09/01
X
X
NTS
827849A2.CDR
TEL: (905)294-6222 FAX: (905)201-2098
INT: http://www.GEindustrial.com/pm
215 ANDERSON AVENUE,
MARKHAM, ONT., CANADA, L6E 1B3
827849A3.CDR
FLEXLOGIC OPERANDS
AUX UV1
FUNCTION:
AUX UV1 BLOCK:
AUX UV1 SIGNAL
SOURCE:
AUX UV1 MINIMUM
VOLTAGE:
AUX UV1 DPO
AUX UV1 OP
AUX UV1 PKP
RUN
SETTING
SETTING
AUX UV1 CURVE:
AUX UV1 DELAY:
AUX UV1 PICKUP:
SETTING
Enabled=1
SETTING
SETTING
Off=0
AUX VOLT Vx
Vx Minimum
Vx Pickup
t
V
<
<
AND
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...