![GE UR Series L90 Скачать руководство пользователя страница 712](http://html.mh-extra.com/html/ge/ur-series-l90/ur-series-l90_instruction-manual_131900712.webp)
B-60
L90 Line Current Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
A911
...Repeated for Frequency Rate of Change 2
A922
...Repeated for Frequency Rate of Change 3
A933
...Repeated for Frequency Rate of Change 4
Restricted Ground Fault (Read/Write Grouped Setting) (6 modules)
A960
Restricted Ground Fault 1 Function
0 to 1
---
1
F102
0 (Disabled)
A961
Restricted Ground Fault 1 Source
0 to 5
---
1
F167
0 (SRC 1)
A962
Restricted Ground Fault 1 Pickup
0.005 to 30
pu
0.001
F001
80
A963
Restricted Ground Fault 1 Slope
0 to 100
%
1
F001
40
A964
Restricted Ground Fault 1 Delay
0 to 600
s
0.01
F001
0
A965
Restricted Ground Fault 1 Reset Delay
0 to 600
s
0.01
F001
0
A966
Restricted Ground Fault 1 Block
0 to 4294967295
---
---
F001
0
A968
Restricted Ground Fault 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A969
Restricted Ground Fault 1 Events
0 to 1
---
1
F102
0 (Disabled)
A96A
...Repeated for Restricted Ground Fault 2
A974
...Repeated for Restricted Ground Fault 3
A97E
...Repeated for Restricted Ground Fault 4
A988
...Repeated for Restricted Ground Fault 5
A992
...Repeated for Restricted Ground Fault 6
IEC 61850 received analog settings (read/write) (32 modules)
AA00
IEC 61850 GOOSE analog 1 default value
–1000000 to 1000000
---
0.001
F060
1000
AA02
IEC 61850 GOOSE analog input 1 mode
0 to 1
---
1
F491
0 (Default Value)
AA03
IEC 61850 GOOSE analog input 1 units
---
---
---
F207
(none)
AA05
IEC 61850 GOOSE analog input 1 per-unit base
0 to 999999999.999
---
0.001
F060
1
AA07
...Repeated for IEC 61850 GOOSE analog input 2
AA0E
...Repeated for IEC 61850 GOOSE analog input 3
AA15
...Repeated for IEC 61850 GOOSE analog input 4
AA1C
...Repeated for IEC 61850 GOOSE analog input 5
AA23
...Repeated for IEC 61850 GOOSE analog input 6
AA2A
...Repeated for IEC 61850 GOOSE analog input 7
AA31
...Repeated for IEC 61850 GOOSE analog input 8
AA38
...Repeated for IEC 61850 GOOSE analog input 9
AA3F
...Repeated for IEC 61850 GOOSE analog input 10
AA46
...Repeated for IEC 61850 GOOSE analog input 11
AA4D
...Repeated for IEC 61850 GOOSE analog input 12
AA54
...Repeated for IEC 61850 GOOSE analog input 13
AA5B
...Repeated for IEC 61850 GOOSE analog input 14
AA62
...Repeated for IEC 61850 GOOSE analog input 15
AA69
...Repeated for IEC 61850 GOOSE analog input 16
AA70
...Repeated for IEC 61850 GOOSE analog input 17
AA77
...Repeated for IEC 61850 GOOSE analog input 18
AA7E
...Repeated for IEC 61850 GOOSE analog input 19
AA85
...Repeated for IEC 61850 GOOSE analog input 20
AA8C
...Repeated for IEC 61850 GOOSE analog input 21
AA93
...Repeated for IEC 61850 GOOSE analog input 22
AA9A
...Repeated for IEC 61850 GOOSE analog input 23
AAA1
...Repeated for IEC 61850 GOOSE analog input 24
AAA8
...Repeated for IEC 61850 GOOSE analog input 25
AAAF
...Repeated for IEC 61850 GOOSE analog input 26
AAB6
...Repeated for IEC 61850 GOOSE analog input 27
AABD
...Repeated for IEC 61850 GOOSE analog input 28
AAC4
...Repeated for IEC 61850 GOOSE analog input 29
AACB
...Repeated for IEC 61850 GOOSE analog input 30
AAD2
...Repeated for IEC 61850 GOOSE analog input 31
AAD9
...Repeated for IEC 61850 GOOSE analog input 32
Table B–9: MODBUS MEMORY MAP (Sheet 52 of 72)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...