GE Multilin
L90 Line Current Differential System
6-15
6 ACTUAL VALUES
6.3 METERING
6
6.3.2 DIFFERENTIAL CURRENT
PATH: ACTUAL VALUES
METERING
87L DIFFERENTIAL CURRENT
The metered current values are displayed for all line terminals in fundamental phasor form. All angles are shown with
respect to the reference common for all L90 devices; that is, frequency, source currents, and voltages. The metered pri-
mary differential and restraint currents are displayed for the local relay.
Terminal 1 refers to the communication channel 1 interface to a remote L90 at terminal 1. Terminal 2 refers
to the communication channel 2 interface to a remote L90 at terminal 2.
87L DIFFERENTIAL
CURRENT
LOCAL IA:
0.000 A
0.0°
MESSAGE
LOCAL IB:
0.000 A
0.0°
MESSAGE
LOCAL IC:
0.000 A
0.0°
MESSAGE
TERMINAL 1 IA:
0.000 A
0.0°
MESSAGE
TERMINAL 1 IB:
0.000 A
0.0°
MESSAGE
TERMINAL 1 IC:
0.000 A
0.0°
MESSAGE
TERMINAL 2 IA:
0.000 A
0.0°
MESSAGE
TERMINAL 2 IB:
0.000 A
0.0°
MESSAGE
TERMINAL 2 IC:
0.000 A
0.0°
MESSAGE
IA DIFF. CURRENT:
0.000 A
0.0°
MESSAGE
IA RESTR. CURRENT:
0.000 A
MESSAGE
IB DIFF. CURRENT:
0.000 A
0.0°
MESSAGE
IB RESTR. CURRENT:
0.000 A
MESSAGE
IC DIFF. CURRENT:
0.000 A
0.0°
MESSAGE
IC RESTR. CURRENT:
0.000 A
MESSAGE
IG DIFF. CURRENT:
0.000 A
0.0°
MESSAGE
IG RESTR. CURRENT:
0.000 A
NOTE
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...