![GE UR Series L90 Скачать руководство пользователя страница 172](http://html.mh-extra.com/html/ge/ur-series-l90/ur-series-l90_instruction-manual_131900172.webp)
5-34
L90 Line Current Differential System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
Use independent ports for IEC 61850 communication and take care when configuring the settings,
else loss of protection or misoperation of the relay can result.
The L90 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over Ethernet. The L90 operates as an IEC 61850 server. The
Remote inputs and outputs
section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
The main transmission menu is shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
sets the time between GSSE or GOOSE messages when there are no remote out-
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state
heartbeat
time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
setting is applicable to GSSE, fixed L90 GOOSE, and configurable GOOSE.
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
GSEE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The
GSSE ID
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
string identifies the GSSE message to the receiving device. In L90 releases previous to 5.0x, this name string was repre-
sented by the
RELAY NAME
setting.
GSSE / GOOSE
CONFIGURATION
TRANSMISSION
MESSAGE
RECEPTION
TRANSMISSION
GENERAL
MESSAGE
GSSE
MESSAGE
FIXED GOOSE
MESSAGE
CONFIGURABLE
GOOSE
GENERAL
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
Range: 1 to 60 s in steps of 1
GSSE
GSSE FUNCTION:
Enabled
Range: Enabled, Disabled
MESSAGE
GSSE ID:
GSSEOut
Range: 65-character ASCII string
MESSAGE
DESTINATION MAC:
000000000000
Range: standard MAC address
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...