B-50
L90 Line Current Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
7896
PMU 1 Phase B Voltage Test Angle
-180 to 180
°
0.05
F002
-12000
7897
PMU 1 Phase C Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
7899
PMU 1 Phase C Voltage Test Angle
-180 to 180
°
0.05
F002
120
789A
PMU 1 Auxiliary Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
789C
PMU 1 Auxiliary Voltage Test Angle
-180 to 180
°
0.05
F002
0
789D
PMU 1 Phase A Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
789F
PMU 1 Phase A Current Test Angle
-180 to 180
°
0.05
F002
-1000
78A0
PMU 1 Phase B Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
78A2
PMU 1 Phase B Current Test Angle
-180 to 180
°
0.05
F002
-13000
78A3
PMU 1 Phase C Current Test Magnitude
0 to 9.999
kA
0.001
F003
1000
78A5
PMU 1 Phase C Current Test Angle
-180 to 180
°
0.05
F002
11000
78A6
PMU 1 Ground Current Test Magnitude
0 to 9.999
kA
0.001
F004
0
78A8
PMU 1 Ground Current Test Angle
-180 to 180
°
0.05
F002
0
78A9
PMU 1 Test Frequency
20 to 70
Hz
0.001
F003
60000
78AB
PMU 1 Test df/dt
-10 to 10
Hz/s
0.01
F002
0
Phasor Measurement Unit Recording Values (Read Only) (4 modules)
7900
PMU 1 Available Records
0 to 65535
---
1
F001
0
7901
PMU 1 Second Per Record
0 to 6553.5
---
0.1
F001
0
7903
PMU 1 Last Cleared Date
0 to 400000000
---
1
F050
0
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
7914
PMU Network Reporting Function
0 to 1
---
1
F102
0 (Disabled)
7915
PMU Network Reporting ID Code
1 to 65534
---
1
F001
1
7916
PMU TCP port number
1 to 65535
---
1
F001
4712
7917
PMU UDP port number 1
1 to 65535
---
1
F001
4713
7918
PMU UDP port number 2
1 to 65535
---
1
F001
4714
Phasor Measurement Unit Calibration (Read/Write Setting) (4 modules)
7919
PMU Va Calibration Angle
-5 to 5
°
0.05
F002
0
791A
PMU Va Calibration Magnitude
95 to 105
%
0.1
F002
1000
791B
PMU Vb Calibration Angle
-5 to 5
°
0.05
F002
0
791C
PMU Vb Calibration Magnitude
95 to 105
%
0.1
F002
1000
791D
PMU Vc Calibration Angle
-5 to 5
°
0.05
F002
0
791E
PMU Vc Calibration Magnitude
95 to 105
%
0.1
F002
1000
791F
PMU Vx Calibration Angle
-5 to 5
°
0.05
F002
0
7920
PMU Vx Calibration Magnitude
95 to 105
%
0.1
F002
1000
7921
PMU Ia Calibration Angle
-5 to 5
°
0.05
F002
0
7922
PMU Ia Calibration Magnitude
95 to 105
%
0.1
F002
1000
7923
PMU Ib Calibration Angle
-5 to 5
°
0.05
F002
0
7924
PMU Ib Calibration Magnitude
95 to 105
%
0.1
F002
1000
7925
PMU Ic Calibration Angle
-5 to 5
°
0.05
F002
0
7926
PMU Ic Calibration Magnitude
95 to 105
%
0.1
F002
1000
7927
PMU Ig Calibration Angle
-5 to 5
°
0.05
F002
0
7928
PMU Ig Calibration Magnitude
95 to 105
%
0.1
F002
1000
7929
PMU Sequence Voltage Shift Angle
-180 to 180
°
30
F002
0
792A
PMU Sequence Current Shift Angle
-180 to 180
°
30
F002
0
Phasor Measurement Unit Triggering (Read/Write Setting) (4 modules)
7970
PMU 1 User Trigger
0 to 4294967295
---
1
F300
0
Phasor Measurement Unit Current Trigger (Read/Write Setting) (4 modules)
7980
PMU 1 Current Trigger Function
0 to 1
---
1
F102
0 (Disabled)
7981
PMU 1 Current Trigger Pickup
0.1 to 30
pu
0.001
F001
1800
7982
PMU 1 Current Trigger Pickup Time
0 to 600
s
0.01
F001
10
7983
PMU 1 Current Trigger Dropout Time
0 to 600
s
0.01
F001
100
7984
PMU 1 Current Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
798A
PMU 1 Current Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
798B
PMU 1 Current Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Table B–9: MODBUS MEMORY MAP (Sheet 42 of 72)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...